INSP-Final Inspection | 12/10/2004 | 12/10/2004 | 12/10/2004 | A | PASS |
Rick Jackson
|
|
|
Final okay 12/10/2004 9:03:13 AM
|
DOC - Permit Finaled | 12/10/2004 | 12/10/2004 | 12/10/2004 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 12/10/2004 9:03:40 AM
|
INSP-Final Inspection | 12/8/2004 | 12/9/2004 | 12/9/2004 | A | FAIL |
Rick Jackson
|
|
|
Burl; Phone #: ###-#### Internet Inspection Request from: Jan Rice Need approved plans; horn instead of horn/stobe; duct detectors to be supervisory per plans 12/9/2004 10:33:55 AM
|
INSP-Final Inspection | 12/8/2004 | 12/8/2004 | 12/8/2004 | P | FAIL |
Rick Jackson
|
|
|
Burl; Phone #: ###-#### Internet Inspection Request from: Jan Rice Need maps; zones defined; approved plans; account not active; sprinkler flow switch on bottom of pipe 12/8/2004 5:02:43 PM
|
Issue and Print Permit | | | 11/3/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 11/2/2004 | | |
|
|
|
|
Sprinkler Plan Check | 11/2/2004 | | 11/2/2004 | | PASS |
Bill Alexander
|
|
|
Revised most demanding/remote area piping.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/2/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/2/2004 | | |
|
|
|
|
Inspection Record Card- Fire | 11/2/2004 | | 11/2/2004 | | DONE |
|
|
|
|
Telephone call | | | 11/2/2004 | | DONE |
|
|
|
Left message for Greg that permit is ready & fees///11/02/04 3:55pm BAS
|
INSP-Sprinkler Rough-in | 10/22/2004 | 10/22/2004 | 10/22/2004 | A | PART |
Rick Jackson
|
|
|
EQ, sidewalls and hangers on 2nd floor okay 10/22/2004 10:53:37 AM
|
INSP-Sprinkler Rough-in/Hydro | 10/20/2004 | 10/20/2004 | 10/20/2004 | P | FAIL |
Rick Jackson
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Sidewalls need to be 4-6 inches below ceiling; straps on second floor; EQ riser; hydro okay FDC will need hydro 10/20/2004 4:05:50 PM
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 10/20/2004 | | |
|
|
|
not tm but fire
|
FIR-Aging Inspection | 6/24/2004 | 6/24/2004 | 6/24/2004 | | PASS |
Rick Jackson
|
|
|
Building still under construction 6/24/2004 7:11:40 AM
|
Sprinkler Plan Check | 3/23/2004 | | 3/25/2004 | | PASS |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 3/25/2004 | | 3/25/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/25/2004 | | DONE |
|
|
|
|
Telephone call | | | 3/25/2004 | | DONE |
|
|
|
spoke with Greg -- permit is ready.,
|
Issue permit | | | 3/25/2004 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 3/16/2004 | | 3/25/2004 | | DONE |
|
|
|
|
Miscellaneous action | | | 3/24/2004 | | DONE |
|
|
|
Called designer (12:08 pm) and indicated the plans were returned to him. Requested full plans back with the faxed resubmittal documents implemented in the plans or attached.
|
Plan resubmittals received | | | 3/23/2004 | | DONE |
|
|
|
|
Issue and Print Permit | | | 3/19/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/16/2004 | | 3/18/2004 | | PART |
Bill Alexander
|
|
|
Some structural clarifications that affect sprinkler positions and locations needed.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/18/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/18/2004 | | 3/18/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/18/2004 | | DONE |
|
|
|
|
Telephone call | | | 3/18/2004 | | DONE |
|
|
|
spoke with Greg -- permit is ready
|
Application received | | | 3/16/2004 | | |
|
|
|
|