INSP-Alarm Testing | 5/11/2004 | 5/13/2004 | 5/13/2004 | P | PASS |
Troy Cobbley
|
|
|
Fire alarm finaled 5/13/2004 2:59:14 PM
|
DOC - Permit Finaled | 5/13/2004 | 5/13/2004 | 5/13/2004 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 5/13/2004 2:59:25 PM
|
Alarm Plan Check | | | 3/31/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/31/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/31/2004 | | 3/31/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/31/2004 | | DONE |
|
|
|
|
Telephone call | | | 3/31/2004 | | DONE |
|
|
|
permit ready and fee due
|
Issue and Print Permit | | | 3/31/2004 | | DONE |
|
|
|
|
Telephone call | | | 3/30/2004 | | DONE |
|
|
|
Left a message for voltage drop calculations.
|
Plan resubmittals received | | | 3/29/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 3/26/2004 | | FAIL |
|
|
|
Resubmittal required. Building has 44 sprinkler heads, replacement of the FACP must comply with IFC 2000. 20 or more sprinkler heads requires remote monitoring. I also informed him of a pull station requirement on the interior stair, he will add it and resubmit. No comments were generated.
|
Application received | | | 3/23/2004 | | |
|
|
|
|
Plan assigned to (Mary) | 3/23/2004 | | | | |
|
|
|
|