Permit Information
Permit NumberFIR04-00196
StatusVoid/No Violation
Name FIRE SENTRY SYSTEMS
Site Address 101 S CAPITOL BLVD
Project Namealm - 5th floor US BANK
Customer Number 
ePlanReview 
Description
The scope will be defined upon receipt of the resubmittal. 6/1/2004 - Scope of work defined as "5th floor preaction control panel replacement. A listed addressable releasing control panel is being installed to activate the pre-action control valve for the computer room, based upon two smoke detectors alarming. The supplemental panel is being monitored by the main fire alarm system for alarm and trouble.

There is no associated building permit.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permit VOIDED  10/27/2004 DONE
Received a phone call from John Lopez, Fire Sentry, that the client has backed out of making the changes as per the permitted plans. Therefore he has requested that I "VOID" the permit.
FIR-Aging Inspection9/24/20049/24/20049/24/2004 FAIL
DetailsTroy Cobbley
per john with fire sentry this job has ben canceled. I told him to contact mary to get permit voided. 9/24/2004 12:30:32 PM
FIR-Aging Inspection9/24/20049/24/20049/24/2004 FAIL
DetailsTroy Cobbley
per john with fire sentry this job has ben canceled. I told him to contact mary to get permit voided. 9/24/2004 12:30:32 PM
Issue and Print Permit  6/25/2004 DONE
PLANS/APPL TAKEN TO FRONT DESK  6/23/2004 DONE
Inspection Record Card- Fire6/23/2004 6/23/2004 DONE
Telephone call  6/23/2004 DONE
permit ready and fee due
Permit Ready to Issue  6/23/2004 DONE
Alarm Plan Check  6/23/2004 PASS
Approved pending field inspection of fire alarm permit comments.
Miscellaneous action  6/11/2004 DONE
Received voltage drop calculations from John Lopez at Fire Sentry
Miscellaneous action  6/11/2004 DONE
Received manufacturer's cut sheet for Notifier pull station from Loren.
Plan resubmittals received  6/10/2004  
Alarm Plan Check  6/1/2004 FAIL
Resubmittal required. Faxed comments to John Lopez 6/1/2004.
Plan resubmittals received  5/19/2004 DONE
Alarm Plan Check  3/26/2004 FAIL
Resubmittal required. Faxed comments to John Lopez.
Application received  3/23/2004  
Plan assigned to (Mary)3/23/2004