Permit Information
Permit NumberFIR04-00235
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 200 N 4TH ST
Project NameSPR UG TERRACE PLAZA
Customer Number 
ePlanReview 
Description
(IDAHO CENTRAL CREDIT UNION)(TERRACE PLAZA) To locate the existing underground fire service supply line, feeding a basement fire sprinkler system, in an existing Type IIIB structure, to install and outside accessible Post Indicator type control valve which shall be provided with supervision/monitoring. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD03-01830.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/15/20057/15/20057/15/2005PPASS
DetailsForrest France
Permit finaled.
INSP-Sprinkler Rough-in/Hydro5/3/20045/4/20045/4/2004APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 5/3/2004 at 1:18:01 PM. Contact: ###-####. The UG main actually runs to the east as shown plans; the new PIV was installed north of the sidewalk, not on the south side as shown on plans; the UG main is four inch and according to Sam of TVFP the main is reduced at an unknown location to three inch where it entrers the basement to the riser 5/4/2004 1:11:28 PM
Issue and Print Permit  4/23/2004 DONE
Application received  4/16/2004  
Plan assigned to (Bill)4/16/2004 4/16/2004 DONE
Sprinkler Plan Check4/16/2004 4/16/2004 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  4/16/2004 DONE
Inspection Record Card- Fire4/16/2004 4/16/2004 DONE
Permit Ready to Issue  4/16/2004 DONE
Telephone call  4/16/2004 DONE
permit ready and fee due