Permit Information
Permit NumberFIR04-00236
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 413 N ALLUMBAUGH ST
Project NameSPR SAGE MEDICAL
Customer Number 
ePlanReview 
Description
(Sage Medical Shell - BLD03-02970 * Dr. David Kent - BLD04-00026 - 7,160 ft/2 * Dr. Steve Bushi - BLD04-00027 - 1,487 ft/2 * Personal Solutions - BLD04-00028 - 1,733 ft/2) To install a dry pipe fire sprinkler system with a looped main, throughout a new 10,380 ft/2 one story, Type VB, multiple tenant medical office building. Underground fire service supply was installed under FIR04-00164. Related building permits are referenced above. Fire sprinklers have been used for area increase. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-02970 (Shell).
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/18/200411/18/200411/18/2004APASS
DetailsTroy Cobbley
Fire sprinkler finaled
DOC - Permit Finaled11/18/200411/18/200411/18/2004APASS
DetailsTroy Cobbley
Finaled by inspector at 11/18/2004 10:23:54 AM
INSP-Final Inspection11/9/200411/9/200411/9/2004PFAIL
DetailsTroy Cobbley
Need breaker locks on the bell, heater and air compressor breakers. Need riser room made to be 1 hour. Test devices for fire alarm interconnection.
INSP-Final Inspection11/5/200411/8/200411/8/2004ACANC
DetailsTroy Cobbley
To be rescheduled with fire alarm final 11/8/2004 3:26:47 PM
INSP-Sprinkler Rough-in/Hydro11/5/200411/5/200411/5/2004PPART
DetailsTroy Cobbley
Overhead hydro test passed. Forward flush of backflow passed. 24 hour air test started at 2:30 with 41 1/2 psi on the guage. 11/5/2004 2:41:03 PM
INSP-Sprinkler Rough-in/Hydro11/3/200411/4/200411/4/2004AFAIL
DetailsTroy Cobbley
Overhead hydro test failed. 11/4/2004 12:29:26 PM
INSP-Final Inspection10/27/200410/29/200410/29/2004ACANC
DetailsTroy Cobbley
Wrong permit called in for hydro test. See underground supply line permit for entry. 10/29/2004 2:28:59 PM
INSP-Supply line flush10/27/200410/28/200410/28/2004AFAIL
DetailsTroy Cobbley
Inspection was for a hydro test. No test done due to faulty pump and leaks. Will try for afternoon 10/28/2004 12:12:01 PM
INSP-Sprinkler Rough-in10/27/200410/28/200410/28/2004PCANC
DetailsTroy Cobbley
Contact: Brian - 24 Air Test, Would like to start the air test after the Hydro test.; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
INSP-Sprinkler Rough-in/Hydro10/7/200410/11/200410/11/2004PCANC
DetailsTroy Cobbley
24 Hr Air Test; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
INSP-Sprinkler Rough-in/Hydro10/5/200410/7/200410/7/2004ACANC
DetailsTroy Cobbley
To be rescheduled for monday per Brian 10/7/2004 11:12:07 AM
INSP-Sprinkler Rough-in/Hydro8/30/20049/1/20049/1/2004AFAIL
DetailsTroy Cobbley
Not all of the hangers have been removed from the cross webbing of the trusses. In one location the hanger attachment is not scewed all the way into the truss 9/1/2004 10:10:58 AM
INSP-Sprinkler Rough-in8/25/20048/26/20048/26/2004APASS
DetailsTroy Cobbley
fire sprinklers are ok to cover. After Bill had a chance to review the submittal provided by the contractor for hanging sprinkler it was found that the cross webbing may not support the sprinkler piping. Contractor to provide verification 8/26/2004 9:10:15 AM
INSP-Sprinkler Rough-in8/23/20048/24/20048/24/2004AFAIL
DetailsTroy Cobbley
Still need verification that the hanger attachments is ok to use in 2 x 4 8/24/2004 3:45:56 PM
INSP-Sprinkler Rough-in8/19/20048/23/20048/23/2004ACANC
DetailsTroy Cobbley
Contact: Nate; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
INSP-Sprinkler Rough-in/Hydro8/20/20048/23/20048/23/2004APART
DetailsTroy Cobbley
Provide sprinklers or insulation in the west overbuild side pockets. Provide missing earthquake bracing and sprig-up as marked on plans. Provide verification that sidesammys will work in 2 x 4's. 8/23/2004 2:09:15 PM
INSP-Sprinkler Rough-in8/19/20048/20/20048/19/2004PCANC
DetailsTroy Cobbley
Contact: Nate; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
Sprinkler Plan Check8/4/2004 8/6/2004 PASS
DetailsBill Alexander
Plan assigned to (Bill)8/4/2004 8/6/2004 DONE
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  8/6/2004 DONE
Permit Ready to Issue  8/6/2004  
Telephone call  8/6/2004 DONE
left mess that permit is ready
Issue and Print Permit  8/6/2004 DONE
Plan resubmittals received  8/4/2004  
INSP-Sprinkler Rough-in7/29/20047/30/20047/30/2004PFAIL
DetailsTroy Cobbley
Resubmit plans to city of boise for review of piping modifications. Do not cover pipe until PASS on re-inspection. Piping hangers and earthquake bracing shall be made to top where the loading was designed. See review note #71. Provide verification of single truss supports per review note #67. Provide verification of use of sidewinders supporting 4" main in 2x4 members. See review note #75. Provide verification that 2x4boards being used for trapeze meet nfpa 13 section 9. No items inspected other than those listed above. 7/30/2004 2:19:48 PM
INSP-Sprinkler Rough-in7/28/20047/30/20047/29/2004ACANC
DetailsTroy Cobbley
Jobsite Contact: Nate; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
Issue and Print Permit  5/10/2004 DONE
Sprinkler Plan Check5/6/2004 5/7/2004 PASS
DetailsBill Alexander
2nd review. No Fee
Plan assigned to (Bill)5/6/2004 5/7/2004 DONE
PLANS/APPL TAKEN TO FRONT DESK  5/7/2004 DONE
Permit Ready to Issue  5/7/2004 DONE
Telephone call  5/7/2004 DONE
left mess that permit is ready
Plan resubmittals received  5/6/2004 DONE
Issue permit  4/26/2004 DONE
Plan assigned to (Bill)4/16/2004 4/23/2004 DONE
Sprinkler Plan Check4/16/2004 4/23/2004 PART
DetailsBill Alexander
Enough to start, but need corrections and related addressed in the attached review comments.
PLANS/APPL TAKEN TO FRONT DESK  4/23/2004 DONE
Permit Ready to Issue  4/23/2004 DONE
Inspection Record Card- Fire4/23/2004 4/23/2004 DONE
Telephone call  4/23/2004 DONE
Spoke with Ross and told him that permit is ready & fees///4/23/04 9:50am
Application received  4/16/2004