INSP-Final Inspection | 10/22/2004 | 10/22/2004 | 10/22/2004 | A | PASS |
Rick Jackson
|
|
|
Hi Rick, Try ###-#### pager # 3006 Thanks, Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble
|
INSP-Final Inspection | 10/22/2004 | 10/22/2004 | 10/22/2004 | A | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 10/22/2004 | 10/22/2004 | 10/22/2004 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 10/22/2004 8:52:15 AM
|
INSP-Final Inspection | 10/20/2004 | 10/20/2004 | 10/20/2004 | P | PART |
Rick Jackson
|
|
|
Hi Rick, We have the doors working and F/S all been gone thru. thanks Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble Need to verify door closures to OR's with fire alarm; all other items corrected - need NFPA 72 record of completion 10/20/2004 4:03:19 PM
|
INSP-Final Inspection | 10/11/2004 | 10/12/2004 | 10/12/2004 | A | FAIL |
Rick Jackson
|
|
|
OR 11 has detectors overspaced; dampers at south area of 2 hour wall need to be on zone 5; detector 25 too close to diffuser; circuit 4 voltage drop too much 10/12/2004 12:33:26 PM
|
INSP-Final Inspection | 10/7/2004 | 10/7/2004 | 10/7/2004 | P | PART |
Rick Jackson
|
|
|
Tested the area of east annex - okay; will need to test area west of 2 hour wall 10/8/2004 7:59:46 AM
|
FIR-Aging Inspection | 9/22/2004 | 9/22/2004 | 9/22/2004 | | PASS |
Rick Jackson
|
|
|
This project is still under construction 9/22/2004 9:49:12 AM
|
Plan assigned to (Mary) | 4/22/2004 | | 6/23/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 6/23/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/23/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 6/23/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/23/2004 | | 6/23/2004 | | DONE |
|
|
|
|
Telephone call | | | 6/23/2004 | | DONE |
|
|
|
Left message for Jim that permit si ready & fees///6/23/04 2:50pm BAM
|
Issue and Print Permit | | | 6/23/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 6/10/2004 | | |
|
|
|
|
Telephone call | | | 5/5/2004 | | DONE |
|
|
|
Call in to Mike Kutz (CH2MHill) to inquire about the visuals located in teh stairwells. Mike is out of the office until the 17th, I discussed it with Duane, he was unaware. I stated I would address it in the comments and resolve it that way.
|
Alarm Plan Check | | | 5/5/2004 | | FAIL |
|
|
|
Resubmittal required. Faxed to Jim Shilton 5/5/2004
|
Application received | | | 4/22/2004 | | |
|
|
|
|