Permit Information
Permit NumberFIR04-00250
StatusFinaled
Name PROTEX
Site Address 6801 N GARY LN
Project Namealm -RIVER GLEN JR HIGH SCHOOL
Customer Number 
ePlanReview 
Description
To add one H/S to a corridor that has been split by double acting doors added to afford visual coverage for notification appliances per NFPA 72 for corridor spacing. The existing required manual system includes sprinkler monitoring, fire/smoke damper control, HVAC shutdown and notification throughout.

9/30/2004 - Revised Scope of work: The double acting doors that have been installed in the corridor are glass. The concept is that the existing H/Ss located in the corridor (see attached partial plans) provide sufficient coverage. The PDS Fire Inspector shall field verify the existing H/S afford the proper coverage (visible from all areas in the corridor). In the event that the existing H/S do afford the coverage, comments #6 and #7 will not apply. In the event the PDS Fire Inspector has reason to believe the existing H/S coverage does not afford the appropriate coverage, then comments #6 and #7 shall apply and the Notice of Correction will stand.

The associated building permit (BLD 04-00038) is to remodel classroom to create another science lab on the second floor of an existing Jr. High School. Work includes new mechanical exhaust system, lab sinks and separate fume hood. Building is fully fire sprinklered and no separations are required for Group E lab. Other work includes new double acting doors across corridor which are not permitted to latch or lock. All work per approved plans and attachments. All fire sprinkler work per N.F.P.A. 13 as regulated by the Fire Dept. Fire Sprinklers used for area. (River Glen Jr. High School)(Science Room remodel) *
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/13/200410/13/200410/13/2004PPASS
DetailsTroy Cobbley
finaled 10/13/2004 2:15:30 PM
DOC - Permit Finaled10/13/200410/13/200410/13/2004PPASS
DetailsTroy Cobbley
Finaled by inspector at 10/13/2004 2:15:34 PM
INSP-Final Inspection10/7/200410/7/200410/7/2004PFAIL
DetailsTroy Cobbley
New a/v has been removed but now there is a trouble on nac circuit 2 area E 10/7/2004 4:24:36 PM
INSP-Conference10/4/200410/5/200410/5/2004PCANC
DetailsTroy Cobbley
Work is not complete yet per Rob 10/5/2004 3:01:29 PM
CHANGE STATUS TO (ISS)  10/4/2004 DONE
Alarm Plan Check  9/30/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  9/30/2004 DONE
Permit Ready to Issue  9/30/2004 DONE
Inspection Record Card- Fire9/30/2004 9/30/2004 DONE
Telephone call  9/30/2004 DONE
Spoke with Rob and told him that permit is ready & no fees///9/30/04 10:06am BAS
Plan resubmittals received  9/29/2004 DONE
Received a copy of the existing second floor corridor H/S locations. The new set of double doors are glass and if there is sufficient coverage from the existing appliances, there will be no FA modifications required in the corridor.
INSP-Conference8/26/20048/27/20048/26/2004PCANC
DetailsTroy Cobbley
This is Robs Cell number; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
Telephone call  8/10/2004 DONE
Spoke with Marv Merkel (Eidam). The panel was designed and installed areound 1###-####. NFPA 72 (93) does not have a requirement for sychronization, but does have a requirement for the temporal audiblity. The remodeled spaces were reviewed under NFPA 72 2002 which require sychronization and temporal alarming. The request is the affected areas should be brought up to code, it this is not possible (panel does not support it, etc.) a letter from Marv would surfice explaining the non-conformance, and include all pertinent information such as the panel manufacturer and model.
INSP-Final Inspection7/27/20047/28/20047/28/2004PFAIL
DetailsTroy Cobbley
Syncronize strobes. See review note #7. Provide temporal for horns. See review note #6. Provide map for the facp per review note #3. 7/28/2004 4:07:10 PM
INSP-Final Inspection7/27/20047/28/20047/27/2004ACANC
DetailsTroy Cobbley
Please Call the office one hour befor inspection if possiable. Thank you Terry; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
Issue and Print Permit  5/14/2004 DONE
Plan assigned to (Mary)4/27/2004 5/12/2004 DONE
Alarm Plan Check  5/12/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  5/12/2004 DONE
Inspection Record Card- Fire5/12/2004 5/12/2004 DONE
Permit Ready to Issue  5/12/2004 DONE
Telephone call  5/12/2004 DONE
permit ready and fee due
Miscellaneous action  5/4/2004 DONE
Request from Terry (Protex) to have plans left at front desk so she can insert the requested information.
Telephone call  5/3/2004 DONE
Left a message requesting the BLDG permit #.
Miscellaneous action  5/3/2004 DONE
Faxed request for additional information. Bldg permit #, site plan and additional application information that was not included on the original application.
Application received  4/27/2004