INSP-Final Inspection | 8/10/2005 | 8/10/2005 | 8/11/2005 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Conference | 8/8/2005 | 8/8/2005 | 8/8/2005 | P | DONE |
Troy Cobbley
|
|
|
Review new fryer dimensions. It appears that it will provide the required 6" clearance when installed. The BBQ at the other end of the hood will be relocated under the hood. These items to be verified when new fryer is installed.
|
FIR-Aging Inspection | 8/3/2005 | 8/3/2005 | 8/5/2005 | | NR |
Troy Cobbley
|
|
|
I left a written notice with the owner. Notice stated "Per inspection performed on 6/18/04 the appliances do not meet the clearance requirements of the International Mechanical Code Section 507.12 of the 2000 edition. This item must be corrected by 8/12/05 or actions will be taken to shutdown the cooking line effected by the hood/suppression system as noted above." I was not well received.
|
INSP-Final Inspection | 6/16/2004 | 6/18/2004 | 6/18/2004 | A | FAIL |
Troy Cobbley
|
|
|
Provide clearance per the IMC, between the appliances and the ends of the hood. 6/18/2004 10:23:38 AM
|
Application received | | | 4/29/2004 | | |
|
|
|
|
Issue and Print Permit | | | 4/29/2004 | | DONE |
|
|
|
|