Permit Information
Permit NumberFIR04-00257
StatusFinaled
Name SUPERIOR FIRE
Site Address 1142 N ORCHARD
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/10/20058/10/20058/11/2005PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Conference8/8/20058/8/20058/8/2005PDONE
DetailsTroy Cobbley
Review new fryer dimensions. It appears that it will provide the required 6" clearance when installed. The BBQ at the other end of the hood will be relocated under the hood. These items to be verified when new fryer is installed.
FIR-Aging Inspection8/3/20058/3/20058/5/2005 NR
DetailsTroy Cobbley
I left a written notice with the owner. Notice stated "Per inspection performed on 6/18/04 the appliances do not meet the clearance requirements of the International Mechanical Code Section 507.12 of the 2000 edition. This item must be corrected by 8/12/05 or actions will be taken to shutdown the cooking line effected by the hood/suppression system as noted above." I was not well received.
INSP-Final Inspection6/16/20046/18/20046/18/2004AFAIL
DetailsTroy Cobbley
Provide clearance per the IMC, between the appliances and the ends of the hood. 6/18/2004 10:23:38 AM
Application received  4/29/2004  
Issue and Print Permit  4/29/2004 DONE