Permit Information
Permit NumberFIR04-00260
StatusFinaled
Name ADT SECURITY SERVICES INC
Site Address 703 S PHILLIPPI ST
Project Namealm - Phillippi House
Customer Number 
ePlanReview 
Description
To extend an existing fire alarm system into the new addition. Single station smoke detectors are to be interconnected per IFC 2000 907.2.10.3, as this R-4 residence is for Health and Welfare, (Roger Gehrke) per Section 16.03.22500.07 of the "Rules for Licensed Residential and Assisted Living Facilities in Idaho", system smoke detectors are required in each sleeping room, office, living room, hallway, family room, etc.

The associated building permit (BLD 03-00675) is to add 1,117 sq.ft. of new floor area with a 600 sq.ft. covered carport attached to an existing 2,690 sq.ft. R-4 occupancy. Work to include installation of two new restrooms, residence room break room. Note: The maximum state licensing for this facility is eight people and two staff. The maximum number of occupants who live in this residence is eight people. If this occupant load is exceeded the installation of a NFPA 13-D or 13-R fire sprinkler system is required per IBC Section 907.2.9. Planning states this building can not be converted to a multi-family unit, there can not be two kitchens. All construction per the approved plans and attached comment list. Note: Fire alarm system per IFC Section 907. MJP Mariana Leahu Addition...
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/12/20047/13/20047/13/2004PPASS
DetailsTroy Cobbley
Fire alarm finaled 7/13/2004 4:18:02 PM
DOC - Permit Finaled7/13/20047/13/20047/13/2004PPASS
DetailsTroy Cobbley
Finaled by inspector at 7/13/2004 4:18:08 PM
INSP-Final Inspection7/9/20047/12/20047/12/2004PFAIL
DetailsTroy Cobbley
Sound level in the west bedroom does not meet 75dba 7/13/2004 9:44:49 AM
INSP-Final Inspection6/30/20047/2/20047/2/2004PFAIL
DetailsTroy Cobbley
Provide smoke detector in front corridor per approved plans. Sound levels do not meet review note requirements in new addition. 7/2/2004 10:36:30 AM
INSP-Final Inspection6/23/20046/24/20046/24/2004PFAIL
DetailsTroy Cobbley
Fire alarm panel was not operating and is not on a dedicated circuit 6/24/2004 4:03:22 PM
Issue permit  5/27/2004 DONE
Permit Ready to Issue  5/21/2004 DONE
Inspection Record Card- Fire5/21/2004 5/21/2004 DONE
Telephone call  5/21/2004 DONE
left mess that permt is ready
Plan assigned to (Mary)4/30/2004 5/20/2004 DONE
Alarm Plan Check  5/20/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  5/20/2004 DONE
Application received  4/30/2004