Case Summary | | | 9/15/2008 | | DONE |
|
|
|
|
DOC - Permit Finaled | 5/28/2004 | 5/28/2004 | 5/28/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 5/28/2004 5:12:14 PM
|
INSP-Final Inspection | 5/26/2004 | 5/28/2004 | 5/28/2004 | P | PASS |
Rick Jackson
|
|
|
###-#### peak or ###-####
|
Issue and Print Permit | | | 5/26/2004 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/25/2004 | | DONE |
|
|
|
|
Telephone call | | | 5/25/2004 | | DONE |
|
|
|
left a message for Bill -- permit is ready.
|
Permit Ready to Issue | | | 5/25/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/25/2004 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
Plan resubmittals received | | | 5/20/2004 | | DONE |
|
|
|
|
INSP-Final Inspection | 5/13/2004 | 5/14/2004 | 5/14/2004 | A | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given with dave millers permission as long as a 24-hr/7-day/wk fire watch is in place until the fire alarm system has been finaled. Per Chris with Dollar Tree, United Security (###-####) has been hired. Items to be corrected include: Sample tubes on the duct smoke detectors are too short. Provide correct lenght tubes. Provide tamper switches on all anti-freeze loop control valves. Resubmit plans showing the additional control valve in the Dollar Tree space. Provide building map with correct device addresses. Provide cover on the electrical connections for the FACP. Provide connection to the hood suppression system and test. PIV supervisory signal lactched. Change to non-latching. Provide minimum 8.4 AH battery for the 12-volt side of the FACP. Test flow switch. Monitoring company does not have account set up for new alarm system/device addresses. Get account set up and retest all devices prior to calling for final inspection. 5/14/2004 1:47:12 PM
|
Plan assigned to (Mary) | 5/5/2004 | | 5/10/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 5/10/2004 | | DONE |
|
|
|
Received fire alarm (FA) application from Bill Herbert (Peak Alarm) via fax. I called Bill and we discussed each item on the application to clarify the information he was submitting.
|
Alarm Plan Check | | | 5/10/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
Inspection Record Card- Fire | 5/10/2004 | | 5/10/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/10/2004 | | DONE |
|
|
|
|
Telephone call | | | 5/10/2004 | | DONE |
|
|
|
permit ready and fee due
|
Issue and Print Permit | | | 5/10/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/7/2004 | | FAIL |
|
|
|
Duct detectors are 12V (system voltage) not 120VAC. Duct detectors not individually annunciated. CSHQA advised to revised plans by Monday 5/10/04.
|
Plan resubmittals received | | | 5/7/2004 | | DONE |
|
|
|
|
Miscellaneous action | | | 5/5/2004 | | DONE |
|
|
|
Faxed request for additional FA permit application information.
|
Application received | | | 5/5/2004 | | |
|
|
|
|