Permit Information
Permit NumberFIR04-00275
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 150 N CAPITOL BLVD
Project NameSPR CITY HALL ENTRANCE RAMP
Customer Number 
ePlanReview 
Description
(CITY HALL ENTRANCE RAMP) * To install an extension of a fire sprinkler system connected to the dry system in Building 1, for the City Hall drive through (basement) access ramp. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work. This permit is not attached to any building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/25/20048/25/20048/25/2004APASS
DetailsRick Jackson
Permit finaled as it meets one minute requirement 8/25/2004 9:55:45 AM
DOC - Permit Finaled8/25/20048/25/20048/25/2004APASS
DetailsRick Jackson
Finaled by inspector at 8/25/2004 9:55:26 AM
INSP-Final Inspection6/30/20047/1/20047/1/2004PFAIL
DetailsRick Jackson
Mick; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Need calc's for capacity of the complete dry system in basement; trip tested and got full stream at test orifice at 4 minutes and at 55 seconds water reached orifice but not a full steady stream 7/1/2004 4:10:29 PM
INSP-Sprinkler Rough-in6/3/20046/4/20046/4/2004APASS
DetailsRick Jackson
todd- ###-#### hydro and r/i okay 6/4/2004 10:25:29 AM
Issue and Print Permit  5/21/2004 DONE
Sprinkler Plan Check5/20/2004 5/20/2004 PASS
Details
Plans approved with comments
PLANS/APPL TAKEN TO FRONT DESK  5/20/2004 DONE
Details
Permit Ready to Issue  5/20/2004  
Issue and Print Permit  5/13/2004 DONE
Plan assigned to (Bill)5/10/2004 5/11/2004 DONE
Sprinkler Plan Check5/10/2004 5/11/2004 PART
DetailsBill Alexander
Review Code: IFC-2000, NFPA 13-2002
Project Type: Existing, Addition
Occupancy Group: S-2
Construction Type: II-B
Area: 1,900-ft/2
System: Dry Pipe
System Design: Ordinary Group 1 Hazard
Head Count/Type: 38 - Tyco Series "TY-B," SSU, S.R., 5.6 K-factor, (½"), TY3151
Submitted By: Simplex/Grinnell - Tom Easton
Phone: ###-#### Fax: ###-####

Re-Submittals Of The Following Items Are Required:
1. Dry System Water Delivery. The existing dry system has been expanded. Provide dry system water delivery calculations. Calculations for dry system water delivery shall be provided and based on the hazard shown in NFPA 13, Table 11.2.3.9.1. (NFPA 13:11.2.3.9)

2. Working Plans-System Capacity. The existing dry system has been expanded. "Working plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and shall show those items from the following list that pertain to the design of the system: Approximate capacity in gallons of each dry pipe system." (NFPA 13:14.1.3(17)

3. Working Plans-Required Pitch. Plans shall include reference to requirements of pitch. NFPA 13:8.15.2.3.1. (IFC 105.4.2, 901.2, BMC 7-01-50-901.2.

4. Working Plans-Inspectors Test. Provide the total Inspectors Test piping/appurtenance in detail on the plans. (NFPA 13:14.1.3 (43), IFC 901.2)

5. Working Plans-Elevations. Provide clarification of existing main elevation from the floor and/or deck and the new 4" main. It appears that no elevation change was provided in the calculations on the 4", 0'-8½" elevation change. Calculations provide only 12'-0" which is addressed between nodes 10 to CON for the 3" main change, between nodes 6 and 7). (NFPA 13:14.1.3 (43), IFC 901.2)

6. General Notes-Unrelated Paragraph Addressing. The plans general notes have paragraphs addressing issues that are totally unrelated to this projects works scope, which shall be either crossed out or totally eliminated from the plans. (IFC 105.4.2, 901.2, BMC 7-01-50-901.2.

7. Clarification of Hangers. Provide clarification of 3" main and its required hanger supports for areas addressed with "plaster" ceilings, since Plan #1 does not address this hanger situation clearly or correctly. (IFC 105.4.2, 901.2, BMC 7-01-50-901.2.
PLANS/APPL TAKEN TO FRONT DESK  5/11/2004 DONE
Inspection Record Card- Fire5/11/2004 5/11/2004 DONE
Permit Ready to Issue  5/11/2004 DONE
Telephone call  5/11/2004 DONE
permit ready and fee due
Application received  5/10/2004