FIR-Aging Inspection | 8/3/2005 | 8/3/2005 | 8/3/2005 | | PASS |
Troy Cobbley
|
|
|
finaled
|
INSP-Final Inspection | 8/3/2005 | 8/3/2005 | 8/3/2005 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled per signature on sign off card of Rick Jackson
|
INSP-Final Inspection | 6/7/2004 | 6/9/2004 | 6/9/2004 | A | FAIL |
Rick Jackson
|
|
|
orlen tilby; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Chime by pantry not working; need to test detectors in wall that has patient occupying the room - GC to reschedule when this area can be tested 6/9/2004 11:13:21 AM
|
INSP-Final Inspection | 6/4/2004 | 6/7/2004 | 6/7/2004 | P | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 6/4/2004 at 1:18:02 PM. Contact: ###-####. Inspection cancelled from web by: Barbara Moore
|
Issue and Print Permit | | | 6/3/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 6/2/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/2/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/2/2004 | | 6/2/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 6/2/2004 | | DONE |
|
|
|
|
Telephone call | | | 6/2/2004 | | DONE |
|
|
|
left mess that permit is ready
|
Telephone call | | | 5/27/2004 | | DONE |
|
|
|
Dan McCrea (Synergy), I called to request additional A/V information on the second floor corridors to ensure proper coverage. I stated they could mark up what I have, or bring new. He'll work on it.
|
Telephone call | | | 5/27/2004 | | DONE |
|
|
|
Called Dennis Adams regarding the deferment letter for the 2nd floor. Left a message to please call me.
|
Miscellaneous action | | | 5/26/2004 | | DONE |
|
|
|
Received PDS approval of the upgrade agreement with the condition that the current system is maintainted until the total upgrade occurs.
|
Miscellaneous action | | | 5/25/2004 | | DONE |
|
|
|
Received Dav Millers approval on the deferement letter.
|
Miscellaneous action | | | 5/25/2004 | | DONE |
|
|
|
Routed deferment letter to Jenifer for approval on the building side.
|
Miscellaneous action | | | 5/21/2004 | | DONE |
|
|
|
Routed deferement letter to Dave Miller.
|
Telephone call | | | 5/19/2004 | | DONE |
|
|
|
Left a message for Dan McCrea regarding a letter from Dennis Adams (St. Als) to Dave Miller (BC) requesting a "Deferment of Standards" for the 2nd floor pediatrics. I stated that I needed something that indicates Dave Miller has approved this letter. I asked that he call me.
|
Miscellaneous action | | | 5/19/2004 | | DONE |
|
|
|
Plans on HOLD until receipt of the following: Faxed request for additional information on the application, scope of work, appropriate fa application filled out (they used an old one) and a site plan requirement.
|
Application received | | | 5/11/2004 | | |
|
|
|
|
Plan assigned to (Mary) | 5/11/2004 | | | | |
|
|
|
|