Permit Information
Permit NumberFIR04-00329
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 11311 W CHINDEN BLVD
Project NameSPR-HP bldg 6
Customer Number 
ePlanReview 
Description
quick permit-to replace and existing 6" Central model E dry pipe valve (defective clapper, no replacement parts) with a 6" Reliable model D dry pipe valve.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/15/20046/16/20046/16/2004APASS
DetailsTroy Cobbley
Fire sprinkler finaled. Dry pipe valve operated correctly and alarm points arrived at the facp 6/16/2004 3:28:28 PM
DOC - Permit Finaled6/16/20046/16/20046/16/2004PPASS
DetailsTroy Cobbley
Finaled by inspector at 6/16/2004 3:28:34 PM
Issue and Print Permit  6/2/2004 DONE
Application received  5/27/2004  
Sprinkler Plan Check5/27/2004 5/27/2004 PASS
Approval subject to satisfactory field inspection by PDS. A Fire Alarm permit is required to disconect/reconnect flow monitoring press switch, hi/lo air press and va tamper supv'n.
PLANS/APPL TAKEN TO FRONT DESK  5/27/2004 DONE
Inspection Record Card- Fire5/27/2004 5/27/2004 DONE
Permit Ready to Issue  5/27/2004 DONE
Telephone call  5/27/2004 DONE
left a message for Jeff -- permit is ready.
Plan assigned to (Bill)5/27/2004