INSP-Final Inspection | 9/28/2004 | 9/28/2004 | 9/28/2004 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/28/2004 at 10:21:00 AM. Contact: ###-####.
|
DOC - Permit Finaled | 9/28/2004 | 9/28/2004 | 9/28/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 9/28/2004 4:58:00 PM
|
INSP-Final Inspection | 9/20/2004 | 9/22/2004 | 9/22/2004 | P | FAIL |
Rick Jackson
|
|
|
This is Grants Cell we need to do thei after 3:30 BECAUSE OF SCHOOL BEING IN SESSION THANK YOU HAVE A GREAT DAY!; Phone #: ###-#### Internet Inspection Request from: Terry Owsley All items corrected except the smoke detectors not replaced with Silent Knight 9/22/2004 4:47:31 PM
|
Issue and Print Permit | | | 9/1/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 8/27/2004 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/27/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/27/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/27/2004 | | 8/27/2004 | | DONE |
|
|
|
|
Telephone call | | | 8/27/2004 | | DONE |
|
|
|
Spoke with Shawna and told her that permit is ready & fees///8/27/04 1:40pm bam
|
Plan resubmittals received | | | 8/25/2004 | | |
|
|
|
|
INSP-Final Inspection | 8/20/2004 | 8/20/2004 | 8/20/2004 | A | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given with Dave Millers permission until the fire alarm plans have been resubmitted and the project inspected. 8/20/2004 1:44:47 PM
|
Plan resubmittals received | | | 8/19/2004 | | |
|
|
|
|
INSP-Final Inspection | 8/16/2004 | 8/17/2004 | 8/17/2004 | P | FAIL |
Troy Cobbley
|
|
|
Provide Knox key box. Provide duct smoke detector on HVAC unit #2 for the office area. Sync strobes in the multipurpose room. Test second smoke detector on zone #5 HVAC unit. Verify battery calculations on the facp and nac panels. Verify wiring integrity between nacs and facp. Verify dedicated circuits. Verify that alarm only output is permissable with plan reviewer. 8/17/2004 4:08:20 PM
|
INSP-Final Inspection | 8/11/2004 | 8/13/2004 | 8/13/2004 | P | NR |
Rick Jackson
|
|
|
This is Grants Cell; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Receved call from Grant and they are not ready for inspection; will reschedule when ready 8/13/2004 12:26:50 PM
|
Issue and Print Permit | | | 7/16/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/15/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/15/2004 | | 7/15/2004 | | DONE |
|
|
|
|
Telephone call | | | 7/15/2004 | | DONE |
|
|
|
left mess that permit is ready
|
Alarm Plan Check | | | 7/14/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/14/2004 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 6/18/2004 | | 7/14/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/13/2004 | | DONE |
|
|
|
|
Miscellaneous action | | | 6/24/2004 | | DONE |
|
|
|
Discussed the "portable" issue with Mike Otto and Dave Miller. Dave Miller is willing to accept the new fire alarm system in the main school building and allow the portables to be upgraded when remodeled or relocated. I spoke with John Rimbey (Mulder) and he will contact Dave Miller and include the correspondance in the next submittal.
|
Alarm Plan Check | | | 6/22/2004 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Rob Ahten 6/22/04.
|
Application received | | | 6/18/2004 | | |
|
|
|
|