Permit NumberFIR04-00370
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 7009 W FRANKLIN RD
Project NameSPR B.K.WEIGHT RM
Customer Number 
ePlanReview 
Description
(Bishop Kelly High School)(Weight Room/Athletic Training Center Addition) * To construct a 3,865-ft/2, Type II-B single story athletic training center addition to the existing gymnasium building. This building is fully fire sprinklered for area. This fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-00705.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/4/20048/4/20048/4/2004APASS
DetailsTroy Cobbley
Fire sprinkler permit finaled
DOC - Permit Finaled8/4/20048/4/20048/4/2004PPASS
DetailsTroy Cobbley
Finaled by inspector at 8/4/2004 11:46:27 AM
INSP-Sprinkler Rough-in/Hydro7/22/20047/22/20047/22/2004PPART
DetailsTroy Cobbley
Hydro test OK. 7/22/2004 11:18:46 AM
INSP-Sprinkler Rough-in/Hydro7/22/20047/22/20047/22/2004PPASS
DetailsTroy Cobbley
Sprinkler rough-in OK. Need new hydraulic sticker, spare heads and tape off of sprinkler uprights to final. 7/22/2004 3:46:36 PM
Permit Ready to Issue  6/30/2004  
Issue and Print Permit  6/30/2004 DONE
Plan assigned to (Bill)6/21/2004 6/29/2004 DONE
Sprinkler Plan Check6/25/2004 6/29/2004 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  6/29/2004 DONE
Inspection Record Card- Fire6/29/2004 6/29/2004 DONE
Telephone call  6/29/2004 DONE
left mess that permit is ready
Plan resubmittals received  6/25/2004  
Sprinkler Plan Check6/21/2004 6/23/2004 FAIL
DetailsBill Alexander
1. Provide existing riser details incorporating pertinent devices that are required and an integral part of a required system required to verify calculations and current code issues. (BMC 7-01-50, IFC 901.2, IFC-2000:105.2.1, 105.4.2, 901.2, NFPA 13:4.3.1(30)

2. Provide a site plan that addresses the Fire Department Access, street the underground is tapped onto, any outside control locations, fire hydrant/s locations/distances, etc. (BMC 7-01-50, IFC 901.2, IFC-2000:105.2.1, 105.4.2, 901.2 NFPA 13:4.3.1(28)

3. Provide the total area of protection this system you're tapping into is protecting. (BMC 7-01-50, IFC 901.2, IFC-2000:105.2.1, 105.4.2, 901.2, NFPA 13:4.3.1(14)

4. Provide some basic history on the existing system attaching. This should include the system design and approximate year the system was installed. (BMC 7-01-50, IFC 901.2, IFC-2000:105.2.1, 105.4.2, 901.2)

5. The Fire Sprinkler Cover Sheet provided indicates this (remote) area is obstructed? The additional clarification addresses 14" steel beams and (8 '2' - something) purlins? Provide clearer information addressing the actual "Obstructed Construction" as identified in NFPA 13-2002, page 200, A.3.7.1, of which lists 7 acceptable types. Plans shall include that obstruction information on the floor plan and section details which are legible. (BMC 7-01-50, IFC 901.2, IFC-2000:105.2.1, 105.4.2, 901.2)

6. Building construction is somewhat addressed in your "Section Plan", (of which the floor plan section cut is miss addressing). The earthquake detail which is shown attached to a vertical wall needs more clarification. HDI or "concrete stud" cannot be used in brick, CMU and similar wall construction. This detail does not address through bolts with washers, etc. required for those types of walls. (BMC 7-01-50, IFC 901.2, IFC-2000:105.2.1, 105.4.2, 901.2, NFPA 13:9.1.3.2)

7. Provide clarification of light fixtures and the possible obstruction created by them. (BMC 7-01-50, IFC 901.2, IFC-2000:105.2.1, 105.4.2, 901.2, NFPA 13:9.1.3.2)

8. Provide submittal and or plan clarification of side beam bracket hanger attachment and how this item is attached to the side of a "Z" Purlin. (BMC 7-01-50, IFC 901.2, IFC-2000:105.2.1, 105.4.2, 901.2, NFPA 13:9.1.3.2)

9. Provide detail of how this addition will tap into the existing system which is required and addressed in NFPA 13:4.3.1(21). (BMC 7-01-50, IFC 901.2, IFC-2000:105.2.1, 105.4.2, 901.2, NFPA 13:9.1.3.2)

10. This system area verified may have a large "cushion" but is not an accurate design since actual head spacing is not near the design spacing verifying. This means that friction loss in the calculations do not include the pipe lengths. If proving a maximum spacing, besides verifying area/density/pressure requirements, actual pipe dimensioning and fittings shall be included in the calculations for verification of friction loss for the area designing to, as addressed in NFPA 13: 8.5.2.1, 14.4.4.3.3, 14.4.4.5, and 14.1.3 (34). Provide corrected calculations which correlate. (BMC 7-01-50, IFC 901.2, IFC-2000:105.2.1, 105.4.2, 901.2)
Miscellaneous action  6/23/2004 DONE
Failed plans taken to "Call Desk" for contacting and returning corrections and resubmittals.
Telephone call  6/23/2004 DONE
PLANS FAILED
Application received  6/21/2004