Permit Information
Permit NumberFIR04-00377
StatusFinaled
Name CRANE ALARM COMPANY
Site Address 5680 W GAGE ST
Project Namealm - J&A Enterprises
Customer Number 
ePlanReview 
Description
To replace an existing fire alarm system. The required sprinkler monitoring fire alarm system includes HVAC shutdown, fire/smoke damper control, manual pull stations, non-required automatic detection and notification throughout.

8/13/2004 - Revised scope, Fire/smoke dampers have been deleted and two more HVAC units have been installed requiring HVAC shutdown, therefore the required sprinkler monitoring fire alarm system includes HVAC shutdown, manual pull stations, non-required automatic detection and notification throughout.

The associated building permit (BLD 04-00495) is to remodel an existing 6,420 square foot building that is used as a medical office and for outpatient medical procedures. The number of persons incapable of self-reservation at any one time is limited to five (5). The medical gas system is existing and will be altered. Work is to include 2 restrooms accessible to the disabled, interior nonbearing walls, altered suspended ceilings, millwork, and interior finishes all per the approved drawings, engineering, and plan review report on file. An interior 1-hr wall is due to the owner's request and is NOT a requirement of the building code. The location of fire sprinkler heads shall comply with NFPA 13 as regulated by the Fire Department. **CJW** (J & A ENTERPRISES) This building is fire sprinklered.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/24/20048/24/20048/24/2004APASS
DetailsTroy Cobbley
Fire alarm finaled
DOC - Permit Finaled8/24/20048/24/20048/24/2004APASS
DetailsTroy Cobbley
Finaled by inspector at 8/24/2004 9:46:01 AM
INSP-Final Inspection8/18/20048/20/20048/20/2004ACANC
DetailsTroy Cobbley
Stopped at project. Contractor not ready to go until next week. 8/20/2004 8:20:21 AM
Issue and Print Permit  8/16/2004 DONE
Alarm Plan Check  8/13/2004 PASS
Plan Modification. Inspector finaled 8/10, documents submitted as plan modification to original permit.
PLANS/APPL TAKEN TO FRONT DESK  8/13/2004 DONE
Permit Ready to Issue  8/13/2004 DONE
Telephone call  8/13/2004 DONE
left a message for Brent -- permit is ready.
Inspection Record Card- Fire8/13/2004 8/13/2004 DONE
INSP-Final Inspection8/10/20048/10/20048/10/2004PPASS
DetailsTroy Cobbley
fire alarm finaled 8/10/2004 4:02:11 PM
DOC - Permit Finaled8/10/20048/10/20048/10/2004PPASS
DetailsTroy Cobbley
Finaled by inspector at 8/10/2004 4:02:16 PM
Plan resubmittals received  8/10/2004  
INSP-Final Inspection8/6/20048/9/20048/9/2004ACANC
DetailsTroy Cobbley
PAT; Phone #: ###-#### Internet Inspection Request from: Annette Moore
INSP-Alarm Testing8/4/20048/6/20048/6/2004AFAIL
DetailsTroy Cobbley
Provide approved door hardware on doors marked on drawing sheet A1.1. Provide exit discharge illumination per building review notes #22. Install ceiling tile at sprinkler pendants. Test duct detectors. Relocate ducting at duct detector #1. Provide 30cd strobes in rooms as marked on plans and measure EOL voltage. Provide map at FACP 8/6/2004 1:57:55 PM
INSP-Final Inspection8/5/20048/6/20048/6/2004PCANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 8/5/2004 at 10:34:50 AM. Contact: ###-####.
Telephone call  8/6/2004 DONE
Spoke with Brent Crane from Crane Alarm. Two Horn/strobes were changed in the field due to insufficient coverage. The in-duct detectors and fire smoke dampers were not installed (not required) and the electrician had notes to connect the FA panel to the generator circuit. The battery calculations were acceptable at 24 hours with 5 minute alarm, acceptable with or without the generator circuit.

I requested a resubmittal for the removal of the in-duct detectors and the fire smoke dampers and the horn/strobe appliances that were changed during inspection.

Resubmittal must be submitted to Boise City prior to final of FA permit.
INSP-Final Inspection7/30/20048/3/20047/30/2004ACANC
DetailsTroy Cobbley
pat; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Inspection cancelled from web by: Aimee Hughes
Plan assigned to (Mary)6/22/2004 7/14/2004 DONE
Alarm Plan Check  7/14/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  7/14/2004 DONE
Inspection Record Card- Fire7/14/2004 7/14/2004 DONE
Telephone call  7/14/2004 DONE
permit ready and fee due
Permit Ready to Issue  7/14/2004 DONE
Issue and Print Permit  7/14/2004 DONE
Plan resubmittals received  7/12/2004  
Alarm Plan Check  6/30/2004 FAIL
Resubmittal required. Faxed comments to Brent Crane 6/30.
Application received  6/22/2004