INSP-Final Inspection | 8/24/2004 | 8/24/2004 | 8/24/2004 | A | PASS |
Troy Cobbley
|
|
|
Fire alarm finaled
|
DOC - Permit Finaled | 8/24/2004 | 8/24/2004 | 8/24/2004 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 8/24/2004 9:46:01 AM
|
INSP-Final Inspection | 8/18/2004 | 8/20/2004 | 8/20/2004 | A | CANC |
Troy Cobbley
|
|
|
Stopped at project. Contractor not ready to go until next week. 8/20/2004 8:20:21 AM
|
Issue and Print Permit | | | 8/16/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 8/13/2004 | | PASS |
|
|
|
Plan Modification. Inspector finaled 8/10, documents submitted as plan modification to original permit.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/13/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/13/2004 | | DONE |
|
|
|
|
Telephone call | | | 8/13/2004 | | DONE |
|
|
|
left a message for Brent -- permit is ready.
|
Inspection Record Card- Fire | 8/13/2004 | | 8/13/2004 | | DONE |
|
|
|
|
INSP-Final Inspection | 8/10/2004 | 8/10/2004 | 8/10/2004 | P | PASS |
Troy Cobbley
|
|
|
fire alarm finaled 8/10/2004 4:02:11 PM
|
DOC - Permit Finaled | 8/10/2004 | 8/10/2004 | 8/10/2004 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 8/10/2004 4:02:16 PM
|
Plan resubmittals received | | | 8/10/2004 | | |
|
|
|
|
INSP-Final Inspection | 8/6/2004 | 8/9/2004 | 8/9/2004 | A | CANC |
Troy Cobbley
|
|
|
PAT; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
INSP-Alarm Testing | 8/4/2004 | 8/6/2004 | 8/6/2004 | A | FAIL |
Troy Cobbley
|
|
|
Provide approved door hardware on doors marked on drawing sheet A1.1. Provide exit discharge illumination per building review notes #22. Install ceiling tile at sprinkler pendants. Test duct detectors. Relocate ducting at duct detector #1. Provide 30cd strobes in rooms as marked on plans and measure EOL voltage. Provide map at FACP 8/6/2004 1:57:55 PM
|
INSP-Final Inspection | 8/5/2004 | 8/6/2004 | 8/6/2004 | P | CANC |
Troy Cobbley
|
|
|
Scheduled by a contractor via Hello! on 8/5/2004 at 10:34:50 AM. Contact: ###-####.
|
Telephone call | | | 8/6/2004 | | DONE |
|
|
|
Spoke with Brent Crane from Crane Alarm. Two Horn/strobes were changed in the field due to insufficient coverage. The in-duct detectors and fire smoke dampers were not installed (not required) and the electrician had notes to connect the FA panel to the generator circuit. The battery calculations were acceptable at 24 hours with 5 minute alarm, acceptable with or without the generator circuit.
I requested a resubmittal for the removal of the in-duct detectors and the fire smoke dampers and the horn/strobe appliances that were changed during inspection.
Resubmittal must be submitted to Boise City prior to final of FA permit.
|
INSP-Final Inspection | 7/30/2004 | 8/3/2004 | 7/30/2004 | A | CANC |
Troy Cobbley
|
|
|
pat; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Inspection cancelled from web by: Aimee Hughes
|
Plan assigned to (Mary) | 6/22/2004 | | 7/14/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 7/14/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/14/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/14/2004 | | 7/14/2004 | | DONE |
|
|
|
|
Telephone call | | | 7/14/2004 | | DONE |
|
|
|
permit ready and fee due
|
Permit Ready to Issue | | | 7/14/2004 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/14/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/12/2004 | | |
|
|
|
|
Alarm Plan Check | | | 6/30/2004 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Brent Crane 6/30.
|
Application received | | | 6/22/2004 | | |
|
|
|
|