INSP-Final Inspection | 5/10/2005 | 5/10/2005 | 5/10/2005 | A | PASS |
Forrest France
|
|
|
Fire alarm finaled.
|
INSP-Final Inspection | 5/4/2005 | 5/5/2005 | 5/5/2005 | A | PART |
Forrest France
|
|
|
Final pending test verification of sprinkler waterflow alarm and updated alarm map at panel.
|
INSP-Final Inspection | 5/3/2005 | 5/4/2005 | 5/4/2005 | A | FAIL |
Forrest France
|
|
|
Tested audible fire alarms- need signal verification. Voltage drop OK. No smoke detector at stairwell top. Wrong type detector at kitchen hallway. Need to test all smoke detectors. Need to test waterflow alarms.
|
FIR-Aging Inspection | 10/12/2004 | 10/12/2004 | 10/12/2004 | | PASS |
Rick Jackson
|
|
|
In progress 10/12/2004 7:06:01 AM
|
Telephone call | | | 8/13/2004 | | DONE |
|
|
|
Nick (Synergy) called to state that the architect would like to delete the non-required multi-station smoke detector at the front door. I stated to red-line their plans and I would leave a note in our system to advise RIck of the deletion. I am not requiring a plan modification resubmittal to the permit at this time. If there are changes in the field, Rick may request it at that time.
|
Telephone call | | | 7/13/2004 | | DONE |
|
|
|
Architect at Erstad called to state the duct smoke detector for the make-up air unit is set up to alarm. At this time everytime there is wind, it goes into alarm. Request to change it to a supervisory signal. I explained that the code specifies supervisory, but if the responsible person wants it to alarm, the city has no preference. Therefore, they may change the programming to supervisory and notify Rick Jackson to verify the functionality.
|
Issue permit | | | 7/13/2004 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 6/29/2004 | | 7/12/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 7/12/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/12/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/12/2004 | | 7/12/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/12/2004 | | DONE |
|
|
|
|
Telephone call | | | 7/12/2004 | | DONE |
|
|
|
permit ready and fee due
|
Miscellaneous action | | | 7/8/2004 | | DONE |
|
|
|
Requested cut sheet for the 120VAC smoke detectors being installed in the residence. Nick (Synergy) will work on it.
|
Application received | | | 6/29/2004 | | |
|
|
|
|