Description
To provide multiple station smoke detectors in a residence per IFC and NFPA 72 and to extend the audible component of the existing building fire alarm system into the residence (4th and 5th floors). The required manual fire alarm system includes sprinkler monitoring, required automatic detection, HVAC shutdown, fire/smoke damper control, elevator recall/shutdown and notification throughout.

The associated building permit (BLD 03-02056) is to construct a new 4,338 sq.ft. two story condominium residential unit on the 4th and 5th floors. The fourth floor is approximately 2,388 sq.ft and the fifth floor is approximately 1,950 sq.ft. Work to include the installation of the HVAC, plumbing, electrical interior walls and cabinets. NOTE: The installation of a NFPA 13 fire sprinkler system is required for story increase and can not be used for any other purposes. All construction per the approved plans and attached comment list. MJP MICHAEL RESIDENCE)(VELTEX BLDG-UNIT 402)

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/10/20055/10/20055/10/2005APASS
DetailsForrest France
Fire alarm finaled.
INSP-Final Inspection5/4/20055/5/20055/5/2005APART
DetailsForrest France
Final pending test verification of sprinkler waterflow alarm and updated alarm map at panel.
INSP-Final Inspection5/3/20055/4/20055/4/2005AFAIL
DetailsForrest France
Tested audible fire alarms- need signal verification. Voltage drop OK. No smoke detector at stairwell top. Wrong type detector at kitchen hallway. Need to test all smoke detectors. Need to test waterflow alarms.
FIR-Aging Inspection10/12/200410/12/200410/12/2004 PASS
DetailsRick Jackson
In progress 10/12/2004 7:06:01 AM
Telephone call  8/13/2004 DONE
Nick (Synergy) called to state that the architect would like to delete the non-required multi-station smoke detector at the front door. I stated to red-line their plans and I would leave a note in our system to advise RIck of the deletion. I am not requiring a plan modification resubmittal to the permit at this time. If there are changes in the field, Rick may request it at that time.
Telephone call  7/13/2004 DONE
Architect at Erstad called to state the duct smoke detector for the make-up air unit is set up to alarm. At this time everytime there is wind, it goes into alarm. Request to change it to a supervisory signal. I explained that the code specifies supervisory, but if the responsible person wants it to alarm, the city has no preference. Therefore, they may change the programming to supervisory and notify Rick Jackson to verify the functionality.
Issue permit  7/13/2004 DONE
Plan assigned to (Mary)6/29/2004 7/12/2004 DONE
Alarm Plan Check  7/12/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  7/12/2004 DONE
Inspection Record Card- Fire7/12/2004 7/12/2004 DONE
Permit Ready to Issue  7/12/2004 DONE
Telephone call  7/12/2004 DONE
permit ready and fee due
Miscellaneous action  7/8/2004 DONE
Requested cut sheet for the 120VAC smoke detectors being installed in the residence. Nick (Synergy) will work on it.
Application received  6/29/2004