INSP-Final Inspection | 1/11/2005 | 1/11/2005 | 1/11/2005 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 1/11/2005 | 1/11/2005 | 1/11/2005 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 1/11/2005 4:47:55 PM
|
INSP-Final Inspection | 1/6/2005 | 1/6/2005 | 1/6/2005 | A | FAIL |
Rick Jackson
|
|
|
Need auxiliary sign on drain in mechanical room 1/6/2005 11:15:01 AM
|
INSP-Sprinkler Rough-in/Hydro | 12/3/2004 | 12/3/2004 | 12/3/2004 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/3/2004 at 10:18:14 AM. Contact: ###-####. Solarium area only okay; the mechanical room not completed 12/3/2004 3:15:13 PM
|
INSP-Sprinkler Rough-in/Hydro | 12/1/2004 | 12/1/2004 | 12/1/2004 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/1/2004 at 10:25:37 AM. Contact: ###-####. Sprinkler heads at soffit need to comply with Table 8.6.5.1.2 and remain no more than 12 inches from ceiling 12/1/2004 3:17:07 PM
|
INSP-Sprinkler Rough-in/Hydro | 11/30/2004 | 11/30/2004 | 11/30/2004 | P | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 11/30/2004 at 8:28:02 AM. Contact: ###-####. Double entry - see entry for same date 11/30/2004 3:51:37 PM
|
INSP-Sprinkler Rough-in/Hydro | 11/30/2004 | 11/30/2004 | 11/30/2004 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 11/30/2004 at 8:28:02 AM. Contact: ###-####. Soffit is over 16 inches wide (18.25 inches) and will require pendants - located in the new solarium area 11/30/2004 3:47:55 PM
|
Issue permit | | | 10/12/2004 | | |
|
|
|
|
Sprinkler Plan Check | 9/29/2004 | | 10/11/2004 | | PASS |
Bill Alexander
|
|
|
Plan and Field changes
|
Plan assigned to (Bill) | 9/29/2004 | | 10/11/2004 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/11/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/11/2004 | | 10/11/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/11/2004 | | |
|
|
|
|
Telephone call | | | 10/11/2004 | | DONE |
|
|
|
left ms with rec regarding permit and fees are ready
|
Plan resubmittals received | | | 9/29/2004 | | DONE |
Bill Alexander
|
|
|
Plan/Field Changes.
|
INSP-Sprinkler Rough-in/Hydro | 9/27/2004 | 9/28/2004 | 9/28/2004 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/27/2004 at 12:59:58 PM. Contact: ###-####. Electrical room has temp protection until grid is installed; additional room was added and not shown on plans; head layout in storage and freezer changed due to lights - spacing maintained 9/28/2004 10:37:41 AM
|
Plan resubmittals received | | | 9/28/2004 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 9/16/2004 | 9/17/2004 | 9/17/2004 | A | FAIL |
Rick Jackson
|
|
|
Area B - need heads in electrical room today - has no protection at this time - a new 2 inch main feeds this area due to fire area alarm zones 9/17/2004 8:44:04 AM 9/17/2004 8:44:20 AM
|
INSP-Sprinkler Rough-in/Hydro | 9/16/2004 | 9/16/2004 | 9/16/2004 | P | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/16/2004 at 10:14:21 AM. Contact: ###-####.
|
Inspection Record Card- Fire | 7/20/2004 | | 7/20/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/20/2004 | | DONE |
|
|
|
|
Telephone call | | | 7/20/2004 | | DONE |
|
|
|
permit ready and fee due
|
CHANGE STATUS TO (ISS) | | | 7/20/2004 | | DONE |
|
|
|
|
(F) Reprint permit | | | 7/20/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/19/2004 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 7/19/2004 | | 7/19/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 7/19/2004 | | 7/19/2004 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/19/2004 | | DONE |
|
|
|
|
INSP-Final Inspection | 7/15/2004 | 7/15/2004 | 7/15/2004 | P | PART |
Rick Jackson
|
|
|
Area D only - okay 7/15/2004 1:54:48 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/8/2004 | 7/9/2004 | 7/9/2004 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 7/8/2004 at 8:11:38 AM. Contact: ###-####. Will need cages on heads under duct work and under stairs 7/9/2004 4:15:22 PM
|
Issue and Print Permit | | | 7/6/2004 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 7/1/2004 | | 7/2/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 7/1/2004 | | 7/2/2004 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/2/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/2/2004 | | 7/2/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/2/2004 | | DONE |
|
|
|
|
Telephone call | | | 7/2/2004 | | DONE |
|
|
|
permit ready and fee due
|
Application received | | | 7/1/2004 | | |
|
|
|
|