INSP-Final Inspection | 9/14/2004 | 9/15/2004 | 9/15/2004 | A | PASS |
Troy Cobbley
|
|
|
Fire sprinklers finaled 9/15/2004 2:52:29 PM
|
INSP-Final Inspection | 9/14/2004 | 9/15/2004 | 9/15/2004 | A | PASS |
Troy Cobbley
|
|
|
Fire sprinklers finaled 9/15/2004 2:52:29 PM
|
DOC - Permit Finaled | 9/15/2004 | 9/15/2004 | 9/15/2004 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 9/15/2004 2:52:35 PM
|
DOC - Permit Finaled | 9/15/2004 | 9/15/2004 | 9/15/2004 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 9/15/2004 2:52:35 PM
|
Plan resubmittals received | | | 9/14/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/14/2004 | | 9/14/2004 | | DONE |
Bill Alexander
|
|
|
Field building modification.
|
Plan assigned to (Bill) | 9/14/2004 | | 9/14/2004 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/14/2004 | | DONE |
|
|
|
|
Case Summary | | | 9/14/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/14/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/14/2004 | | 9/14/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/14/2004 | | 9/14/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/14/2004 | | 9/14/2004 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 9/14/2004 | | |
|
|
|
re-issued 9/14/04 BAS
|
(F) Reprint permit | | | 9/14/2004 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in | 8/17/2004 | 8/18/2004 | 8/18/2004 | A | FAIL |
Troy Cobbley
|
|
|
Resubmit plans showing wall changes. Can't use small room rule in will call/ shipping area. See plans for location. More than one pendant off of 1" outlet over restroom 8/18/2004 3:25:04 PM
|
Plan resubmittals received | | | 8/16/2004 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/20/2004 | | DONE |
|
|
|
|
Case Summary | | | 7/19/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 7/16/2004 | | 7/19/2004 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/19/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/19/2004 | | 7/19/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/19/2004 | | DONE |
|
|
|
|
Telephone call | | | 7/19/2004 | | DONE |
|
|
|
permit ready and fee due
|
Plan resubmittals received | | | 7/16/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 7/9/2004 | | 7/12/2004 | | FAIL |
Bill Alexander
|
|
|
Reference Comments
|
Telephone call | | | 7/12/2004 | | DONE |
|
|
|
plans fail
|
Application received | | | 7/9/2004 | | |
|
|
|
|
Plan assigned to (Bill) | 7/9/2004 | | | | |
|
|
|
|