Permit Information
Permit NumberFIR04-00412
StatusFinaled
Name FUTURETECH
Site Address 2895 S FEDERAL WAY
Project Namealm - Stone Mountain Flooring
Customer NumberBLD04-02058
ePlanReview 
Description
To provide a required sprinkler monitoring fire alarm system. The system shall include HVAC shutdown, fire/smoke damper control and elevator recall/shutdown.

The associated building permit (BLD 04-02057) is to construct a new 35,675 square foot, two story, concrete tilt-up shell building and related site improvements. This is a shell building permit only. No occupancy is allowed under this permit. Separate tenant improvement permits will be required to finish this building for occupancy. All construction per the approved plans and attached comment list. DRH03-00073/PC#514-03/JCM Stone Mountain Flooring - (Shell)

The associated building permit (BLD 04-02058) is to finish a 21,045 square foot, two story tenant improvement for Stone Mountain Flooring. This space will include a retail/warehouse area, shipping and receiving area and a second floor office support area. All construction per the approve plans and attached comment list. PC#515-03/JCM Stone Mountain Flooring - (Tenant Improvement)

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Issue and Print Permit  11/4/2004 DONE
Permit Ready to Issue  9/2/2004 DONE
Telephone call  9/2/2004 DONE
Talked to Matt at 11:43 am to let him know that his fire alarm is ready to be picked up
Alarm Plan Check9/1/2004 9/1/2004 PASS
Plan Modification.
PLANS/APPL TAKEN TO FRONT DESK  9/1/2004 DONE
INSP-Final Inspection8/31/20048/31/20048/31/2004APASS
DetailsRick Jackson
DOC - Permit Finaled8/31/20048/31/20048/31/2004APASS
DetailsRick Jackson
Finaled by inspector at 8/31/2004 11:11:19 AM
Plan resubmittals received  8/30/2004 DONE
INSP-Final Inspection8/27/20048/27/20048/27/2004PFAIL
DetailsRick Jackson
LEd not working on AHU 5 detector; need updated maps to reflect changes; resubmittals needed due to initiating circuit changes; monitor elevator power as shown on plans 8/27/2004 4:09:47 PM
Plan assigned to (Mary)7/9/2004 8/6/2004 DONE
Alarm Plan Check  8/6/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  8/6/2004 DONE
Override - Parcel Holds  8/6/2004  
Permit Ready to Issue  8/6/2004 DONE
Override - Parcel Holds  8/6/2004  
Inspection Record Card- Fire8/6/2004 8/6/2004 DONE
Telephone call  8/6/2004 DONE
Left message for Matt that permit is ready & fees///8/6/04 BAM
Issue permit  8/6/2004 DONE
Plan resubmittals received  7/30/2004 DONE
Alarm Plan Check  7/23/2004 FAIL
Resubmittal required. Faxed comments to Matt Casey at Futuretech 7/23
Plan resubmittals received  7/22/2004 DONE
Alarm Plan Check  7/13/2004 FAIL
Resubmittal required. Faxed comments to Matt Casey at Futuretech 7/13
Application received  7/9/2004