Issue and Print Permit | | | 11/4/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/2/2004 | | DONE |
|
|
|
|
Telephone call | | | 9/2/2004 | | DONE |
|
|
|
Talked to Matt at 11:43 on phone let him know his fire alarm permit is ready to pick up
|
Alarm Plan Check | | | 9/1/2004 | | PASS |
|
|
|
Plan Modification.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/1/2004 | | DONE |
|
|
|
|
INSP-Final Inspection | 8/31/2004 | 8/31/2004 | 8/31/2004 | A | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 8/31/2004 | 8/31/2004 | 8/31/2004 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 8/31/2004 11:11:15 AM
|
Plan resubmittals received | | | 8/30/2004 | | DONE |
|
|
|
|
INSP-Final Inspection | 8/27/2004 | 8/27/2004 | 8/27/2004 | P | FAIL |
Rick Jackson
|
|
|
Plans don't install - initiating devices don't match; update maps; resubmit plan mod's; monitor elevator power as shown on plans; need lockout on sprinkler bell breaker; need sign on FACP door; install knox box 8/27/2004 4:13:54 PM
|
Override - Parcel Holds | | | 8/6/2004 | | |
|
|
|
|
Inspection Record Card- Fire | 8/6/2004 | | 8/6/2004 | | DONE |
|
|
|
|
Telephone call | | | 8/6/2004 | | DONE |
|
|
|
Left message for Matt that permit is ready & fees///8/6/04 BAM
|
Issue permit | | | 8/6/2004 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 7/9/2004 | | 8/6/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 8/6/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/6/2004 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 8/6/2004 | | |
|
|
|
|
Permit Ready to Issue | | | 8/6/2004 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 8/6/2004 | | |
|
|
|
|
Plan resubmittals received | | | 7/30/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 7/23/2004 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Matt Casey 8/23/2004.
|
Plan resubmittals received | | | 7/22/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 7/13/2004 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Matt Casey at Futuretech 7/13
|
Application received | | | 7/9/2004 | | |
|
|
|
|
Inspection Record Card- Fire | 8/6/2004 | | | | |
|
|
|
|