INSP-Final Inspection | 1/12/2005 | 1/12/2005 | 1/12/2005 | P | PASS |
Troy Cobbley
|
|
|
Fire alarm finaled 1/12/2005 3:09:27 PM
|
DOC - Permit Finaled | 1/12/2005 | 1/12/2005 | 1/12/2005 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 1/12/2005 3:09:31 PM
|
CHANGE STATUS TO (ISS) | | | 1/12/2005 | | DONE |
|
|
|
already picked up -will bill customer
|
Alarm Plan Check | | | 1/7/2005 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/7/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/20/2004 | | DONE |
|
|
|
|
INSP-Final Inspection | 11/19/2004 | 11/23/2004 | 11/23/2004 | A | FAIL |
Troy Cobbley
|
|
|
Test duct smoke detectors. Provide knox box. Provide signage on door. Multiple pull stations are mounted above 48". See review note #13. Provide a/v in conference room 116 per review note #5. Break room a/v needs to be 30cd to meet code. See approved plans for smoke detector locations that are within 3' of supply diffusers. Resubmit plans showing the two additional duct smoke detectors. Signals are messed up at the monitoring station. All zones need to be retested. Inspection stopped due to amount of items found to be incorrect. There may be additional items when re-inspected. 11/23/2004 10:05:14 AM
|
FIR-Aging Inspection | 11/15/2004 | 11/15/2004 | 11/15/2004 | | NR |
Troy Cobbley
|
|
|
Per Matt they still need to finish connections to duct detectors but should have it called in by the end of the week for inspection 11/15/2004 9:46:20 AM
|
Issue permit | | | 8/16/2004 | | |
|
|
|
|
Plan assigned to (Mary) | 7/12/2004 | | 8/11/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 8/11/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/11/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/11/2004 | | 8/11/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/11/2004 | | DONE |
|
|
|
|
Telephone call | | | 8/11/2004 | | DONE |
|
|
|
left a message for Randy -- permit is ready.
|
Plan resubmittals received | | | 8/2/2004 | | DONE |
|
|
|
|
Alarm Plan Check | 7/26/2004 | | 7/26/2004 | | FAIL |
|
|
|
Resubmiital requried. Faxed comments to Randy Sikkema at ADT.
|
Plan resubmittals received | | | 7/23/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 7/15/2004 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Randy Sikkema 7/15.
|
Application received | | | 7/12/2004 | | |
|
|
|
|