Permit Information
Permit NumberFIR04-00434
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 110 N CURTIS RD
Project NameSPR BRICO OF IDAHO IN-RACKS
Customer Number 
ePlanReview 
Description
BRICO OF IDAHO * To install inrack fire sprinkler protection for combustible liquids storage in high pile racking, located in a Type V-N, 5,865-ft/2 (shown) and 6,772-ft/2 (possible) warehouse space for storage of Class III-A and III-B combustible liquids (Motor Oils, Transmission Fluid, etc.) in containers of 5 gallons or less. This building is fully sprinklered for allowable area increase and high piled hazardous materials storage. This fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-00279.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/27/20048/30/20048/30/2004PPASS
DetailsTroy Cobbley
fire sprinklers finaled 8/30/2004 3:50:37 PM
DOC - Permit Finaled8/30/20048/30/20048/30/2004PPASS
DetailsTroy Cobbley
Finaled by inspector at 8/30/2004 3:50:44 PM
Sprinkler Plan Check8/24/2004 8/30/2004 DONE
DetailsBill Alexander
8/26/2004 Hold plans for faxed resubmittals.

Plans approved on condition: Provide an official signed letter, from De Best Fire Protection (officer) that they, "understand the installation code issues relating to the above IFC requirements and accept a modified fire sprinkler head installation design, and take full responsibility for the protection requirements relating to the in-rack protection as modified and installed."
Plan assigned to (Bill)8/24/2004 8/30/2004 DONE
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  8/30/2004 DONE
Inspection Record Card- Fire8/30/2004 8/30/2004 DONE
Permit Ready to Issue  8/30/2004 DONE
Telephone call  8/30/2004 DONE
permit ready and fee due
Issue and Print Permit  8/30/2004 DONE
INSP-Final Inspection8/26/20048/27/20048/27/2004AFAIL
DetailsTroy Cobbley
Provide revised plans and spare heads of rack type in the head box 8/27/2004 11:08:47 AM
Telephone call  8/27/2004 DONE
Recieved a phone call from Jim Danes (De Best Fire Protection Manager) regarding the resubmittal of plans (8/24/04) lacking correct information and to disregard the resubmittal. 11:15am.
Plan resubmittals received  8/24/2004  
INSP-Sprinkler Rough-in/Hydro8/20/20048/23/20048/23/2004PFAIL
DetailsTroy Cobbley
Wrong sprinkler heads have been installed. Change out heads or resubmit. Hydro test and rough-in OK. Need alarms 8/23/2004 3:00:02 PM
Plan resubmittals received  8/20/2004 DONE
Sprinkler Plan Check8/20/2004 8/20/2004 PASS
Rack reduced and the 2.5 main lifted plan change.
Telephone call  8/20/2004 DONE
Faxed approval of documents submitted and attached set to file plans.
Issue and Print Permit  7/28/2004 DONE
Plan assigned to (Bill)7/23/2004 7/27/2004 DONE
Sprinkler Plan Check7/23/2004 7/27/2004 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  7/27/2004 DONE
Permit Ready to Issue  7/27/2004 DONE
Inspection Record Card- Fire7/27/2004 7/27/2004 DONE
Telephone call  7/27/2004 DONE
Spoke with John and told him that permit is ready & fees///7/27/04 2:15 pm BAM
Application received  7/23/2004