INSP-Final Inspection | 1/27/2005 | 1/28/2005 | 1/28/2005 | P | PASS |
Rick Jackson
|
|
|
Contact: Vance - Needs around 2 PM - please call to confirm.; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley UG riser has been corrected to allow heat to base of UG at sidewalk level; dry uprights installed 1/28/2005 2:06:15 PM
|
DOC - Permit Finaled | 1/28/2005 | 1/28/2005 | 1/28/2005 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 1/28/2005 2:06:19 PM
|
INSP-Sprinkler Rough-in/Hydro | 1/3/2005 | 1/4/2005 | 1/4/2005 | P | PART |
Rick Jackson
|
|
|
1:00 pm; will need to check flows for alarms at fire panel R/I okay; will need to complete dry uprights for final; UG will need heat per resubmittals; need resubmittals for changes to riser and racking 1/4/2005 2:48:19 PM
|
INSP-Sprinkler Rough-in | 1/3/2005 | 1/3/2005 | 1/3/2005 | P | FAIL |
Rick Jackson
|
|
|
Contact: Vance - Walt thru - would like around 1:30 PM - please call to confirm; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Flow switch on east riser not operating properly 1/3/2005 2:57:29 PM
|
INSP-Sprinkler Rough-in/Hydro | 12/30/2004 | 12/30/2004 | 12/30/2004 | P | PART |
Rick Jackson
|
|
|
Contact: vance; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Hydro okay; will do the r/i on 1/3; all control valves locked open; system not supervised 12/30/2004 5:06:24 PM
|
INSP-Final Inspection | 12/30/2004 | 12/30/2004 | 12/30/2004 | P | PART |
Rick Jackson
|
|
|
contact: vance; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Hydro okay; will do r/i on 1/3; all control valves locked open; system not supervised 12/30/2004 5:05:41 PM
|
INSP-Sprinkler Rough-in | 12/30/2004 | 12/30/2004 | 12/30/2004 | P | PART |
Rick Jackson
|
|
|
Contact: Vance - Hydro for 1 pm; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Hydro okay; will do r/i on 1/3; all control valves locked open; system not supervised 12/30/2004 5:05:57 PM
|
FIR-Aging Inspection | 12/24/2004 | 12/24/2004 | 12/27/2004 | | PART |
Rick Jackson
|
|
|
Still under construction 12/27/2004 10:41:02 AM
|
Issue and Print Permit | | | 9/24/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/23/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/23/2004 | | 9/23/2004 | | DONE |
|
|
|
|
Telephone call | | | 9/23/2004 | | DONE |
|
|
|
Spoke with Alisha and told her that permit is ready & fees///9/23/04 2:20pm BAS
|
Sprinkler Plan Check | 9/10/2004 | | 9/22/2004 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/22/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/10/2004 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 7/29/2004 | | 8/11/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 8/9/2004 | | 8/11/2004 | | PART |
Bill Alexander
|
|
|
Resubmittal required.
1. Plan FP4 of 4. Provide complete data submittals on Dry Uprights installing in Warehouse "C". Include the maximum dimension installing. Include the number installing in the "Sprinkler Schedule." NOTE: Partial section on same sheet scales in excess of 4'-0" of upright required. Maximum listed approval length ("B" dimensioning) is 49½". Any length exceeding this length will not be allowed. (4'-0" is the industry standard for maximum listing). Another issue is sprig-ups 4 ft or longer shall be restrained against lateral movement. (NFPA 13:9.3.6.5*, 9.3.5.5)
2. Provide data submittal of the listed water shields installing. (NFPA 13:8.5.5.3.3)
3. Sprinklers in single row "D.1" racks do not meet the location requirements addressed and shown in 12.3.3.1.5(f). Revise and resubmit.
4. Milk Receiving Bay has an area where sprinkler head spacing exceeds the design verified. Revise and resubmit.
5. Building "C" calculations address a remote area of 1025-ft/2 and not 1,500 (minimum required)? Revise and resubmit. Note: Q.R. Reduction allowance does not apply to Chapter 12 "Storage."
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/11/2004 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 8/11/2004 | | 8/11/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/11/2004 | | DONE |
|
|
|
|
Telephone call | | | 8/11/2004 | | DONE |
|
|
|
left a message for John -- permit is ready.
|
Issue and Print Permit | | | 8/11/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/6/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 7/29/2004 | | 8/2/2004 | | FAIL |
Bill Alexander
|
|
|
The data has been moved to a Word document attached to this case.
|
Miscellaneous action | | | 8/2/2004 | | DONE |
|
|
|
Returned failed plans to permit desk for returning.
|
Telephone call | | | 8/2/2004 | | DONE |
|
|
|
Spoke with Alisha and told her that plans failed and need picked up///8/2/04 11:10am BAM
|
Application received | | | 7/29/2004 | | |
|
|
|
|