Permit Information
Permit NumberFIR04-00463
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 9530 W BETHEL CT
Project NameSPR OH BETHEL WAREHOUSE
Customer Number 
ePlanReview 
Description
BETHEL WAREHOUSE * This work is for a "Spec" Warehouse. To install a (fully fire sprinklered), High Piled Combustible Storage system in a new 13,500-ft/2 one story Type III-B shell only building. NOTE: Plans are showing 4 separate tenant spaces with one restroom and two offices with future janitor rooms in each space which will require separate permitting. Separate plans and permits are required for each tenant space. No occupancy is authorized by association with this building permit. Also smoke vents are being roughed-in (not installed) for the future separate tenant spaces. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-00558. Underground fire service supply was permitted separately under FIR04-00384.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/4/200411/4/200411/4/2004PPASS
DetailsTroy Cobbley
Fire sprinkler finaled
DOC - Permit Finaled11/4/200411/4/200411/4/2004PPASS
DetailsTroy Cobbley
Finaled by inspector at 11/4/2004 4:40:27 PM
INSP-Final Inspection11/1/200411/1/200411/1/2004AFAIL
DetailsTroy Cobbley
Certify backflow preventer and new sprinkler system
INSP-Sprinkler Rough-in/Hydro10/6/200410/7/200410/7/2004APASS
DetailsTroy Cobbley
Overhead hydro test passed 10/6/2004 12:22:06 PM
INSP-Sprinkler Rough-in/Hydro10/4/200410/5/200410/5/2004PPART
DetailsTroy Cobbley
Underground hydro test passed. Overhead test failed 10/5/2004 4:19:59 PM
INSP-Sprinkler Rough-in/Hydro9/28/20049/29/20049/29/2004AFAIL
DetailsTroy Cobbley
Overhead sprinkler piping was inspected. Offices, riser and FDC not inspected. I found many sprinkler uprights covered with tape, one upright bent, earthquake bracing was missing and retaining straps missing from one side of the trapeze hangers. See approved plans for specific locations. Underground flush was ok and entry was made under FIR04-00384. 9/29/2004 11:10:41 AM
INSP-Supply line flush9/28/20049/28/20049/28/2004PCANC
DetailsTroy Cobbley
contractor did not have valve key so no flush was done 9/28/2004 4:32:46 PM
Permit Ready to Issue  8/13/2004 DONE
spoke with Jeff -- permit is ready.
Permit Ready to Issue  8/13/2004 DONE
Issue and Print Permit  8/13/2004 DONE
Miscellaneous action  8/12/2004 DONE
Emailed: BETHEL WAREHOUSE, 9530 W. Bethel Ct., FIR04-00463

Jeff, I am looking at this resubmittal and I am taking issue with the following items which will require addressing prior to letting this permit fly full approval.

1. Plan information appears to be lacking since Fire Department Connections is not on the street side of the building, immediately discernible, fully visible and recognizable from the street or nearest point of fire department apparatus accessibility. Provide correction providing this requirement. (BMC 7-01-61, IFC 912.2.2.1, IFC 508.5.4, 903.3.7, 912, NFPA 13:8.16.2.4.6, 7.7.2.3, 8.16.2.4.6)
Your response was basically to meet code in the future? You will have get approval from Dave Miller of proposed "future" relocation of FDC to street side of the building or provide it under this permitted scope of work.

2. The designer has made no consideration in addressing the future smoke heat vent locations and type proposed addressed in the building permit (BLD04-00558) meeting IFC 2306.7. Fire sprinkler head location and spacing shall be designed for future building requirements, since the framing (only) is being installed under this shell permit. Fire sprinkler heads located under "drop" out smoke/heat vents will not be accepted. Verify the type of smoke heat vents proposing to install in the future or verify heads will not be installed beneath. (IFC 105.4.1)
Your addressing of this issues indicates the smoke/heat framing is flush with the deck. This does not address the issue of future use incorporating "shrink" or "drop" out vents which will affect fire sprinkler operations if heads are located beneath. The plan does not show where these frames will be installed (unless it's in the 4 circles on the floor plan) and if so, it would appear fir sprinkler will be affected? Future relocating will be required incorporating respacing and revised calculation approval! You will have to provide a letter from the Architect indicating that no "shrink" or "drop" out smoke heat vents will be installed and if they are, it is acceptable to incorporate a new permitted design for fire sprinklers modifications, calculations with the future T.I./s permits.

3. Provide engineered trapeze hangers supporting east and west cross mains on the plans. (IFC 105.4.1)
You provided a trapeze supported span size but did not provide a complete or correct detail. The trapeze clevis/ring hanger supporting the rod and cross main is not identified as being secured from slippage? The 9.1.1.6.7 and 9.1.1.7.8 addresses using bolts not hangers, which would prevent side to side slippage. You did not address the supported, ring, strap, or clevis hangers on the trapeze as required to be the same size corresponding to the suspended pipe supporting! You need to fax a correct detail incorporating minimum installation code so the installer/s will comply. (NFPA 13:9.1.1.6.5, 9.1.1.6.5)
Sprinkler Plan Check8/12/2004 8/12/2004 PASS
DetailsBill Alexander
Miscellaneous action  8/12/2004 DONE
Took plans to permit desk for calling.
Plan resubmittals received  8/11/2004 DONE
Plan assigned to (Bill)8/3/2004 8/5/2004 DONE
Sprinkler Plan Check8/3/2004 8/5/2004 PART
DetailsBill Alexander
Plans problems needing addressed (see review notes attached).
1. Plan information is lacking since Fire Department Connections is not on the street side of the building, immediately discernible, fully visible and recognizable from the street or nearest point of fire department apparatus accessibility. Provide correction providing this requirement. (BMC 7-01-61, IFC 912.2.2.1, IFC 508.5.4, 903.3.7, 912, NFPA 13:8.16.2.4.6, 7.7.2.3, 8.16.2.4.6)
2. The designer has made no consideration in addressing the future smoke heat vent locations and type requirements addressed in the building permit (BLD04-00558) meeting IFC 2306.7. Fire sprinkler head location and spacing shall be designed for future building requirements, since the framing is being installed under this shell permit. Fire sprinkler heads located under "drop out" smoke/heat vents will not be accepted. Verify the type of smoke heat vents proposing to install in the future or verify heads will not be installed beneath which shall be address under this permit. (IFC 105.4.1)
3. Designer is using a pendant SIN number on and upright head in the Sprinkler Head Legend, FP-2. (IFC 105.4.1)
4. Plans are incomplete. Provide type of fitting incorporating on the lines, riser, mains, etc. (IFC 105.4.1, NFPA 13:14.1.3(21)
5. Plans are incomplete. Provide correct dimensioning of riser which will include pipe sizes. (IFC 105.4.1, NFPA 13:14.1.3(19)
6. Calculations are incomplete for proposed (future) inrack sprinklers demand requirements in addition to the roof system. Provide calculations incorporating a minimum proposed design for inrack sprinklers, which will verify a true demand the designer is actually designing for. (IFC 105.4.1)
7. Provide and show on the plans the required drain for the east side cross main. (IFC 105.4.1, 102.7, NFPA 13:8.15.2.5)
8. Provide engineered trapeze hangers supporting east and west cross mains on the plans. (IFC 105.4.1)
PLANS/APPL TAKEN TO FRONT DESK  8/5/2004 DONE
Inspection Record Card- Fire8/5/2004 8/5/2004 DONE
Permit Ready to Issue  8/5/2004 DONE
Telephone call  8/5/2004 DONE
spoke with Jeff -- permit is ready.
Issue and Print Permit  8/5/2004 DONE
Application received  8/3/2004