INSP-Final Inspection | 12/29/2004 | 12/29/2004 | 12/29/2004 | P | PASS |
Troy Cobbley
|
|
|
Contact: Chris Felty - Please call with time that can meet, would like to do around 10 am; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
|
DOC - Permit Finaled | 12/29/2004 | 12/29/2004 | 12/29/2004 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 12/29/2004 2:31:32 PM
|
Sprinkler Plan Check | 11/10/2004 | | 11/22/2004 | | PASS |
Bill Alexander
|
|
|
New Design/Plans under FIR04-00705.
|
Plan resubmittals received | | | 11/10/2004 | | |
Bill Alexander
|
|
|
Under FIR04-00705.
|
INSP-Conference | 10/19/2004 | 10/19/2004 | 10/19/2004 | P | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given with dave millers permission until the fire sprinkler permit is finaled. Per the signed notice they will have the work completed by January 15, 2005 10/19/2004 4:12:18 PM
|
Telephone call | | | 8/12/2004 | | DONE |
|
|
|
Designer provided (faxed) verification that this is considered a Class C or D Science Lab. Room protection will require a minimum OH-1 design density protection per NFPA 45:4.2.1.1 as directed from NFPA 13:13.8.1.
|
Plan resubmittals received | | | 8/12/2004 | | DONE |
Bill Alexander
|
|
|
Designer provided documentation that the room converting is classified as a true Class C or D science lab.
|
Telephone call | | | 8/12/2004 | | DONE |
|
|
|
Randy Bowron called and requested Fax number for submittal data addressed in review comments #1.
|
Miscellaneous action | | | 8/12/2004 | | DONE |
|
|
|
Emailed to Ranyd Bowron (copied Troy C.) revised review comments addressing requirement in verifying lab is protected to OH-1 occupancy minimum.
|
Sprinkler Plan Check | 8/6/2004 | | 8/9/2004 | | PART |
Bill Alexander
|
|
|
Provide documentation from the school or school district verifying the laboratory unit/s are protected based on Ordinary Hazard (Group 1) occupancies. (NFPA 13:13.8.1, 45:4.2.1.1(b)
|
Plan assigned to (Bill) | 8/6/2004 | | 8/9/2004 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/9/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/9/2004 | | 8/9/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/9/2004 | | DONE |
|
|
|
|
Telephone call | | | 8/9/2004 | | DONE |
|
|
|
left a message for Randy -- permit is ready.
|
Issue permit | | | 8/9/2004 | | DONE |
|
|
|
|
Application received | | | 8/6/2004 | | |
|
|
|
|