Permit Information
Permit NumberFIR04-00469
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 6801 N GARY LN
Project NameSPR RIVER GLEN JR.HIGH SCIENCE
Customer Number 
ePlanReview 
Description
(RIVER GLEN JR. HIGH SCHOOL)(SCIENCE ROOM REMODEL) * To add one sprinkler for the remodel of a classroom to create another science lab on the second floor of an existing Jr. High School. Fire sprinkler work shown is for a corridor that has been split by double acting none latch or lock doors. No other work shown or allowed without corrected submittals. Building is fully fire sprinklered. Fire Sprinklers are used for area. This fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-000138.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/29/200412/29/200412/29/2004PPASS
DetailsTroy Cobbley
Contact: Chris Felty - Please call with time that can meet, would like to do around 10 am; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
DOC - Permit Finaled12/29/200412/29/200412/29/2004PPASS
DetailsTroy Cobbley
Finaled by inspector at 12/29/2004 2:31:32 PM
Sprinkler Plan Check11/10/2004 11/22/2004 PASS
DetailsBill Alexander
New Design/Plans under FIR04-00705.
Plan resubmittals received  11/10/2004  
DetailsBill Alexander
Under FIR04-00705.
INSP-Conference10/19/200410/19/200410/19/2004PPART
DetailsTroy Cobbley
A temporary occupancy was given with dave millers permission until the fire sprinkler permit is finaled. Per the signed notice they will have the work completed by January 15, 2005 10/19/2004 4:12:18 PM
Telephone call  8/12/2004 DONE
Designer provided (faxed) verification that this is considered a Class C or D Science Lab. Room protection will require a minimum OH-1 design density protection per NFPA 45:4.2.1.1 as directed from NFPA 13:13.8.1.
Plan resubmittals received  8/12/2004 DONE
DetailsBill Alexander
Designer provided documentation that the room converting is classified as a true Class C or D science lab.
Telephone call  8/12/2004 DONE
Randy Bowron called and requested Fax number for submittal data addressed in review comments #1.
Miscellaneous action  8/12/2004 DONE
Emailed to Ranyd Bowron (copied Troy C.) revised review comments addressing requirement in verifying lab is protected to OH-1 occupancy minimum.
Sprinkler Plan Check8/6/2004 8/9/2004 PART
DetailsBill Alexander
Provide documentation from the school or school district verifying the laboratory unit/s are protected based on Ordinary Hazard (Group 1) occupancies. (NFPA 13:13.8.1, 45:4.2.1.1(b)
Plan assigned to (Bill)8/6/2004 8/9/2004 DONE
PLANS/APPL TAKEN TO FRONT DESK  8/9/2004 DONE
Inspection Record Card- Fire8/9/2004 8/9/2004 DONE
Permit Ready to Issue  8/9/2004 DONE
Telephone call  8/9/2004 DONE
left a message for Randy -- permit is ready.
Issue permit  8/9/2004 DONE
Application received  8/6/2004