INSP-Final Inspection | 10/5/2004 | 10/6/2004 | 10/6/2004 | P | PASS |
Troy Cobbley
|
|
|
Fire life safety finaled 10/6/2004 2:00:58 PM
|
INSP-Final Inspection | 10/6/2004 | 10/6/2004 | 10/6/2004 | P | PASS |
Troy Cobbley
|
|
|
fire alarm finaled
|
DOC - Permit Finaled | 10/6/2004 | 10/6/2004 | 10/6/2004 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 10/6/2004 2:00:41 PM
|
INSP-Final Inspection | 9/30/2004 | 10/1/2004 | 10/1/2004 | P | FAIL |
Troy Cobbley
|
|
|
Room 317 no longer exists, its now a therapy room. Change description on fire alarm panel.
Provide a visual device in the short corridor on the south side of the nurses station 9/1/2004 3:15:59 PM
|
INSP-Alarm Testing | 9/30/2004 | 10/1/2004 | 9/30/2004 | P | DONE |
Troy Cobbley
|
|
|
thad; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
Miscellaneous action | | | 9/22/2004 | | DONE |
|
|
|
Phone conversation with Nick at Synergy, comment #6 states that the signal shall be temporal. Per NFPA72 6.8.4.1 (commentary in handbook) "...it may be impractical or undesirable to change an existing evacuation signal that is already recognized by occupants and approved by the AHJ." Therefore, the notification appliances that are installed for this permit may be programmed to "signal" to match the existing.
|
Issue and Print Permit | | | 8/30/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 8/27/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/27/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/27/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/27/2004 | | 8/27/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/27/2004 | | 8/27/2004 | | DONE |
|
|
|
|
Telephone call | | | 8/27/2004 | | DONE |
|
|
|
Left message for Kurt that permit is ready & fees///8/27/04 1:45pm BAM
|
Plan assigned to (Mary) | 8/12/2004 | | 8/27/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/26/2004 | | DONE |
|
|
|
Received a copy of the fuel agreement.
|
Plan resubmittals received | | | 8/19/2004 | | DONE |
|
|
|
Received a fax copy of a revised matrix.
|
Plan resubmittals received | | | 8/17/2004 | | DONE |
|
|
|
Received a fax copy of the generator information.
|
Telephone call | | | 8/16/2004 | | DONE |
|
|
|
Request to Nick (Synergy) to send revised matrix. Also require the generator information and fuel agreement.
|
Miscellaneous action | | | 8/16/2004 | | DONE |
|
|
|
Received a fax copy of a revised matrix. Called Nick, general smoke detecotrs do not recall the elevator, he will send a new one.
|
Plan resubmittals received | | | 8/16/2004 | | DONE |
|
|
|
Received a fax copy of a revised matrix. Called Nick, general smoke detecotrs do not recall the elevator, he will send a new one.
|
Application received | | | 8/12/2004 | | |
|
|
|
|