DOC - Permit Finaled | 11/18/2004 | 11/18/2004 | 11/18/2004 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 11/18/2004 10:23:50 AM
|
INSP-Final Inspection | 11/18/2004 | 11/18/2004 | 11/18/2004 | A | PASS |
Troy Cobbley
|
|
|
Fire alarm finaled
|
INSP-Alarm Testing | 11/15/2004 | 11/16/2004 | 11/16/2004 | P | FAIL |
Troy Cobbley
|
|
|
Duct smoke detectors for hvac units 5 and 6 are still not placed per NFPA 72 11/16/2004 3:31:09 PM
|
INSP-Alarm Testing | 11/12/2004 | 11/12/2004 | 11/12/2004 | P | FAIL |
Troy Cobbley
|
|
|
Provide map at facp. Duct detectors are mounted incorrectly. Retest them when done. Provide responding address for fire dept at the monitoring station. Provide nfpa 72 forms 11/12/2004 1:01:21 PM
|
INSP-Alarm Testing | 11/9/2004 | 11/10/2004 | 11/10/2004 | P | FAIL |
Troy Cobbley
|
|
|
The only two items tested are the battery calcs and the phone lines. Both items ok. Started to test sprinkler devices but they did not report to panel. Failed and stopped inspection 11/10/2004 3:27:29 PM
|
Issue permit | | | 11/3/2004 | | |
|
|
|
|
Alarm Plan Check | | | 11/2/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/2/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/2/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/2/2004 | | 11/2/2004 | | DONE |
|
|
|
|
Telephone call | | | 11/2/2004 | | DONE |
|
|
|
Left message for Jack that permit is ready & fees///11/02/04 3:25pm BAS
|
Plan resubmittals received | | | 10/29/2004 | | DONE |
|
|
|
|
Issue and Print Permit | | | 9/1/2004 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 8/12/2004 | | 8/30/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 8/30/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/30/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/30/2004 | | 8/30/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/30/2004 | | DONE |
|
|
|
|
Telephone call | | | 8/30/2004 | | DONE |
|
|
|
PERMIT READY AND FEE DUE
|
Plan resubmittals received | | | 8/25/2004 | | |
|
|
|
|
Alarm Plan Check | | | 8/19/2004 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Jack Schmidt 8/19/2004.
|
Application received | | | 8/12/2004 | | |
|
|
|
|