Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberFIR04-00505
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 7009 W FRANKLIN RD
Project NameSPR BISHOP KELLY HIGH
Customer Number 
ePlanReview 
Description
(BISHOP KELLY HIGH)(PRESIDENT'S OFFICE) To modify existing fire sprinkler protection by removing 6 HSW and add 7 new SSU's and recessed SSP's for the remodel of the (school) president's office area. This work is related to the installation of 12 lineal feet of new non-bearing partition to create two separate offices and to add a new door to the corridor and add a new suspended ceiling with a new roof top HVAC unit serving three offices in the northwest corner of the existing high school per approved plans. This fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-01428.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/27/20057/27/20057/27/2005PPASS
DetailsTroy Cobbley
Permit finaled
(F) Reprint permit  12/22/2004 DONE
INSP-Final Inspection9/28/20049/29/20049/29/2004AFAIL
DetailsTroy Cobbley
Upright sprinkler heads which are spaced too far off of the exterior wall in the cavity have not been addressed. Small room rule can not be used. See nfpa 13; 3.3.20 for definition of a small room. Must have walls and a ceiling. Reinspection fee for fourth inspection for same item applied. 9/29/2004 10:06:46 AM
INSP-Final Inspection9/23/20049/24/20049/24/2004AFAIL
DetailsTroy Cobbley
Approved plans not on site. Per Adam they are in the principals office. The principal, Robert Wehde and I looked in his office and could not find the plans. Inspection failed. Re-inspection fee applied to this project. 9/24/2004 9:30:52 AM
INSP-Final Inspection9/23/20049/24/20049/24/2004AFAIL
DetailsTroy Cobbley
Approved plans not on site. Per Adam they are in the principals office. The principal, Robert Wehde and I looked in his office and could not find the plans. Inspection failed. Re-inspection fee applied to this project. 9/24/2004 9:30:52 AM
Inspection Record Card- Fire9/17/2004 9/17/2004 DONE
Telephone call  9/17/2004 DONE
Spoke with Jeff and told him that permit is ready & no fees///9/17/04 8:11am BAS
Sprinkler Plan Check9/14/2004 9/15/2004 DONE
DetailsBill Alexander
Field changes with failed field inspection.
Miscellaneous action  9/15/2004 DONE
Took resubmittal field changes to Permit Desk for calling. 2nd Review-No Fee
Plan resubmittals received  9/14/2004 DONE
INSP-Final Inspection9/9/20049/9/20049/9/2004PFAIL
DetailsTroy Cobbley
Resubmit plans per review note #8. The addition of the rooftop unit has blocked coverage of the upright sprinkler head. Per the sprinkler head data sheet it appears that three types of sprinkler heads are being used. A 3/8" a 1/2" and a 3/4" are not crossed out on the data sheet. Specify which head is being used and in which location. Provide info and SIN number on the resubmittals. Provide access to the sprinkler heads such as a ladder for verification of specific head type and correct esch. Upright sprinkler heads have less than 1" clearance from ceiling to deflector. See NFPA 13; 8.6.4.1.1.1. Atleast one of the pipe hangers appear to be screwed into partical board above the ceiling. Provide verification this is acceptable and verification the other hangers meet NFPA 13 requirements. Upright heads are spaced 8'-6" off of the exterior wall in the concealed spaced. Provide verification "small room rule" can also be "small cavity rule" or add/relocate uprights. 9/9/2004 3:03:13 PM
Issue permit  8/25/2004 DONE
Plan assigned to (Bill)8/19/2004 8/20/2004 DONE
Sprinkler Plan Check8/20/2004 8/20/2004 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  8/20/2004 DONE
Inspection Record Card- Fire8/20/2004 8/20/2004 DONE
Permit Ready to Issue  8/20/2004 DONE
Telephone call  8/20/2004 DONE
talked with Jeff Anderson that their permit is ready to be picked up and paid
Application received  8/19/2004