Permit Information
Permit NumberFIR04-00513
StatusFinaled
Name MICRON TECHNOLOGY INC FP
Site Address 8000 S FEDERAL WAY
Project NameSPR MICRON BLD 1X 8" DUCT
Customer NumberPCS6400
ePlanReview 
Description
Micron Building #1X - Install (SOD) Bulk Chemical Feed System * To install fire quenching protection (2 nozzles) on each side of a two-hour fire barrier (here known to be the ceiling). This work is related to the installation of the 8" diameter, continuously wrapped, with #M "Firemaster" for a two-hour fire-resistive rated duct wrap fume exhaust duct, from Drum Unload Room #107D to an existing 14" diameter fume exhaust duct above Corridor #100J. NOTE: A similar application quench system is on record as an approved alternate to the required shaft enclosure approved by Dave Miller. This fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-01022.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  8/3/2005 DONE
DOC - Permit Finaled  8/3/2005 DONE
INSP-Final Inspection11/30/200412/1/200412/1/2004PPASS
DetailsRick Jackson
Cell Ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
DOC - Permit Finaled12/1/200412/1/200412/1/2004PPASS
DetailsRick Jackson
Finaled by inspector at 12/1/2004 2:33:00 PM
Issue and Print Permit  10/12/2004 DONE
Inspection Record Card- Fire10/11/2004 10/11/2004 DONE
Permit Ready to Issue  10/11/2004 DONE
Telephone call  10/11/2004 DONE
E-mailed Paul & Max and told them that this permit is ready & fees///10/11/04 7:45am BAS
Sprinkler Plan Check10/6/2004 10/8/2004 PASS
DetailsBill Alexander
Plan assigned to (Bill)10/6/2004 10/8/2004 DONE
PLANS/APPL TAKEN TO FRONT DESK  10/8/2004 DONE
Plan resubmittals received  10/6/2004 DONE
DetailsBill Alexander
Issue and Print Permit  9/21/2004  
Permit Ready to Issue  9/17/2004 DONE
Telephone call  9/17/2004 DONE
E-mailed paul to let him know that permit is ready & fees///9/17/04 8:30am BAS
Sprinkler Plan Check9/14/2004 9/16/2004 PART
DetailsBill Alexander
Provide a correct Nozzle/Head design that meets the approved application protection usage with design.

Provide clarification of required duct draining.
PLANS/APPL TAKEN TO FRONT DESK  9/16/2004 DONE
Inspection Record Card- Fire9/16/2004 9/16/2004 DONE
Plan assigned to (Bill)8/25/2004 9/16/2004 DONE
Plan resubmittals received  9/14/2004 DONE
Telephone call  8/27/2004 DONE
email to Paul & Darla plans failed
Sprinkler Plan Check8/25/2004 8/26/2004 FAIL
DetailsBill Alexander
a. The alternative submitted in BLD04-01022 does not match the design alternative used for BLD99-01573, since the original was approved for a horizontal application and this is for a vertical application. (IFC 105.4) NOTE: No fire permit was not applied for or issued on the original alternative fire protection design, of which was required by City ordinance that took effect, January 1, 1999!

b. Design submitted does not address injection rate flows; relative to airflow which shall be match this project permitting. (IFC 105.3.7, 901.2)

c. This related building scope of work indicates the duct to be continuously wrapped with fire-resistive rated #M Firemaster duct wrap? The design alternative (request) letter dated August 5, 1999 indicates this fire sprinkler alternative is proposed for the elimination of the ducting wrap downstream (of the required 2 hour barrier assembly). The IBC Plan reviewer indicates that the wrap shall be installed. With this requirement, no information was provided on how that separation will be maintained with the required inspection openings to inspect the fire sprinkler heads. (IFC 105.3.7, 901.2, NFPA 13:7.9.12)

d. Building data submittals indicate the incorporation of the FlexHead© system. Provide manufacturers data submittals if incorporating a FlexHead© or similar type system to these ducts as addressed in the related building submittal and original alternative package. Include corrosion prevention requirements where corrosive atmospheres exist, and the duct sprinklers pipe and pipe fittings as being manufactured and installed with corrosion-resistant materials or coated with approved materials. (NFPA 13:3.6.4.1 [definition], 6.2.6.1, 318:4.1.2.6.5 [required])

e. The fire sprinkler head submitted does not meet the approved characteristics as addressed in the original approved alternative package. (Reference item "a" above)

f. Provide a (required) control valve (NFPA 318:4.1.2.6.3) supplying these in-duct heads and provide valve monitoring and supervision (IFC 903.4).

g. This duct quench system will require approved drainage. Provide corrected documents addressing this requirement. (IFC 105.3.7, NFPA 318:4.1.2.6.4*, A.4.1.2.6.4)
Miscellaneous action  8/26/2004 DONE
Took plans to permit desk for calling an returning. Emailed copy of review comments to Paul Marcolina.
Application received  8/25/2004