Permit Information
Permit NumberFIR04-00517
StatusFinaled
Name PROTEX
Site Address 9530 W BETHEL CT
Project Namealm - Bethel Warehouse
Customer Number 
ePlanReview 
Description
To provide a required sprinkler monitoring fire alarm system that includes HVAC shutdown.

The associated building permit (BLD 04-00558) is to construct a 13,500 s.f. one story Type III-B fully fire sprinklered shell only building. Plans are showing 4 separate tenant spaces with one restroom and two office with future janitor rooms in each space. No occupancy is authorized by this permit. Separate plans and permits are required for each tenant space. Smoke vents in each space are being roughed in only under this permit. When smoke vents are to be installed separate plans, engineering and permits will be required. DRH04-00008 Bethel Warehouse *
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/4/200411/4/200411/4/2004PPASS
DetailsTroy Cobbley
Fire alarm finaled
DOC - Permit Finaled11/4/200411/4/200411/4/2004PPASS
DetailsTroy Cobbley
Finaled by inspector at 11/4/2004 4:40:23 PM
INSP-Final Inspection11/1/200411/1/200411/1/2004PFAIL
DetailsTroy Cobbley
Phone line troubles did not go to monitoring station and the duct detectors did not have power
Issue and Print Permit  10/7/2004 DONE
Alarm Plan Check  10/6/2004 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  10/6/2004 DONE
Inspection Record Card- Fire10/6/2004 10/6/2004 DONE
Permit Ready to Issue  10/6/2004 DONE
Telephone call  10/6/2004  
called and left ms w/sec regarding no charge and fire ready to be picked up
Plan resubmittals received  10/5/2004  
Permit Ready to Issue  9/9/2004  
Telephone call  9/9/2004 DONE
left mess that permit is ready
Issue permit  9/9/2004 DONE
Plan assigned to (Mary)8/25/2004 9/8/2004 DONE
Telephone call  9/8/2004 DONE
Left a message for Rob to call me, I need the FACP battery charging info and battery size capacity.
Alarm Plan Check  9/8/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  9/8/2004 DONE
Plan resubmittals received  9/8/2004 DONE
Received battery information (FACP) and matrix.
Plan resubmittals received  9/3/2004 DONE
Per Mary
Alarm Plan Check  9/2/2004 FAIL
Resubmittal required. No comments are issued. The cut sheets for the FACP, smoke detector, pull station and batteries are not included.
Telephone call  9/2/2004 DONE
Left a message for Rob...Resubmittal required. No comments are issued. The cut sheets for the FACP, smoke detector, pull station and batteries are not included. I stated I would accept the cur sheets and an application, but it would count as a resubmittal
Application received  8/25/2004