Permit Information
Permit NumberFIR04-00521
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 601 N PHILLIPPI ST
Project NameSPR STEIN DISTRIBUTING
Customer Number 
ePlanReview 
Description
(STEIN DISTRIBUTING) To extend fire sprinkler protection into 3 storage spaces with High Piled which include an enlarge restroom within an existing 9,315-ft/2 warehouse per approved plans. Fire sprinkler work is related to Work will include new partitions and ceilings, and remodel of restroom to make accessible. This fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-01194.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/7/200410/8/200410/8/2004APASS
DetailsTroy Cobbley
Fire sprinkler finaled 10/8/2004 10:22:05 AM
DOC - Permit Finaled10/8/200410/8/200410/8/2004APASS
DetailsTroy Cobbley
Finaled by inspector at 10/8/2004 10:22:08 AM
Sprinkler Plan Check10/1/2004 10/5/2004 PASS
Hangers incorporated trapeze hanger. Provided engineered Trapeze Hanger attachement.
Miscellaneous action  10/5/2004 DONE
Emailed approval and documents to Inspector Troy Cobbely and Gerald Ebeling (designer).
INSP-Final Inspection9/30/200410/1/200410/1/2004AFAIL
DetailsTroy Cobbley
Provide revised sway bracing calcs to bill alexander. Forward flush passed. Hydro test failed. Rescheduled for this afternoon 10/1/2004 11:34:00 AM
INSP-Sprinkler Rough-in/Hydro10/1/200410/1/200410/1/2004PPASS
DetailsTroy Cobbley
hydro test passed. Need test papers 9/1/2004 3:02:45 PM
Plan resubmittals received  10/1/2004 DONE
Issue permit  9/28/2004 DONE
Sprinkler Plan Check9/23/2004 9/27/2004 PASS
DetailsBill Alexander
Revised sprinkler heads
Plan assigned to (Bill)9/23/2004 9/27/2004 DONE
PLANS/APPL TAKEN TO FRONT DESK  9/27/2004 DONE
Permit Ready to Issue  9/27/2004 DONE
Inspection Record Card- Fire9/27/2004 9/27/2004 DONE
Telephone call  9/27/2004 DONE
Spoke with Broadie and told him that permit is ready & fees///9/27/04 1:30pm BAS
Plan resubmittals received  9/23/2004 DONE
Plan assigned to (Bill)8/26/2004 9/20/2004 DONE
DetailsBill Alexander
Sprinkler Plan Check9/9/2004 9/20/2004 PART
DetailsBill Alexander
September 20, 2004 - Revised K-factor heads to 8.0 and recalculated most demanding remote. Resubmitted fire sprinklers cannot be used in new system piping (reference NFPA 13:8.3.5). Revise and incorporate approved fire sprinklers and resubmit revised plans and submittals addressing the same for areas #1 & 2.
PLANS/APPL TAKEN TO FRONT DESK  9/20/2004 DONE
Permit Ready to Issue  9/20/2004 DONE
Inspection Record Card- Fire9/20/2004 9/20/2004 DONE
Telephone call  9/20/2004 DONE
Spoke with Gerald and told him that permit is ready & fees///9/20/04 12:35pm BAS
Issue permit  9/20/2004 DONE
Plan resubmittals received  9/9/2004 DONE
Sprinkler Plan Check8/26/2004 9/8/2004 FAIL
DetailsBill Alexander
1. Fire sprinkler calculation design most demanding and remote Test #1 does not meet requirements as design indicated in Table 12.1.9.1.2(a). Revise K-factor heads and resubmit. (IFC 105.4, 901.2)

2. Fire sprinkler calculation design most demanding and remote Test #2 does not meet requirements as design indicated in Table 12.1.9.1.2(a). Revise K-factor heads and resubmit. (IFC 105.4, 901.2)

3. Provide and show required draining meeting requirements for all trapped piping. (NFPA 13:8.15.2.5, IFC 102.7)
4. Provide engineered trapezes hangers pipe size and type supporting in meeting the design data incorporating span and weight/load factors per NFPA 13:9.1.1.6.1 and include it on the plans. (IFC 105.4, 901.2)

5. Hanger detail #15 (FP-1) addresses a typical trapeze which also does not clearly address correct engineering. Normal installation with the pipe hanger support to the trapeze is provided with a rod drilled through the trapeze clarified in 9.1.1.6.4, which would prevent hanger slippage at this point of contact. Correct and resubmit. (IFC 105.4, 901.2)

6. Hanger detail #15 (FP-1) addresses a typical trapeze which also does not clearly address correct engineering. Where pipe is suspended from a pipe trapeze of a diameter less than the diameter of the pipe being supported, the rings, straps, or clevis hangers of the size, corresponding to the suspended pipe, shall be used on both ends as addressed in 9.1.1.6.5. Correct and resubmit. (IFC 105.4, 901.2)

7. Designer does not clarify which "Wood Vertical Mount Sammy" incorporating. GST 25-380 & GST 30 (Wood, 3/8" Vertical Mount) are UL listed up to 4". GST 20 is UL listed up to 2 ½". No other "Sammy" Wood, 3/8" Vertical Mount all-thread rod anchoring system is listed. A GST 20 (listed for up to 2 ½" pipe only) can be installed into the center of the lower cord of a composite joist only. Penetration of the upright center web is permitted by some joist manufacturers. Truss manufacturer installation point approvals shall be available on demand by the IFC Fire/Life Safety Inspector during inspection. NOTE: Special nut drivers are available and designed to be used with the Sammy Super Screw™ anchoring system. Nut drivers must be used for installation to meet warranty and listing requirements since the driver spins free on the screw after installation is complete and reduces over-torquing and screw (snap) failure. Pre-drilling may be required by joist manufacturers. If required, pre-drill pilot 1/8" smaller than root diameter of fastener. Consult "Sammy" predrilled hole size table plus the truss manufacturer installation requirements prior to installations. Clarify and resubmit. (IFC 105.4, 901.2)


8. The 6" bulk main is missing a required E.Q. brace. Correct and resubmit. (IFC 105.4, 901.2)

9. Plan sheet FP-1 "Remote Design Information", Remote Area #2, "Hazard is incorrect. Correct and resubmit.
Miscellaneous action  9/8/2004 DONE
Took failed plans to "Permit Desk" for calling and returning.
Telephone call  9/8/2004 DONE
PERMIT FAILED CALLED FOR PICK UP
Telephone call  9/7/2004 DONE
Called designer (Gerrald Ebling) 2:25 PM, regarding a problem with incomplete "Fire Sprinkler Cover Sheet", since "Storage" information is lacking on page 1 and page 2. Stopped review until more information is provided in order to verifiy IFC Chapter 23 requirements.
Application received  8/26/2004