INSP-Final Inspection | 8/5/2005 | 8/8/2005 | 8/8/2005 | A | PASS |
Troy Cobbley
|
|
|
Fire sprinkler permit finaled
|
INSP-Final Inspection | 7/19/2005 | 7/20/2005 | 7/20/2005 | A | FAIL |
Troy Cobbley
|
|
|
Need to verify that the exposed combustibles located above the outside canopies has met requirements of NFPA 13 for combustible concealed spaces.
|
Sprinkler Plan Check | 7/5/2005 | | 7/7/2005 | | PASS |
Bill Alexander
|
|
|
Changed compressor from a 30 gal 1HP K1S-30UMS to a 17gal 1HP K1S-BS due to system volume size.
|
Plan resubmittals received | | | 7/5/2005 | | |
|
|
|
|
INSP-Final Inspection | 6/29/2005 | 7/1/2005 | 7/1/2005 | A | PART |
Troy Cobbley
|
|
|
Trip tested Dry System #1 and #2. Both sent in the correct alarm signals. Contractor still needs to correct overspaced and blocked heads under canopy, wrong air compressors installed, butterfly control valve on dry system #1 broke, need to blank off the switches controlling the air compressors, need to trip test the east dry system.
|
INSP-Sprinkler Rough-in/Hydro | 6/29/2005 | 6/30/2005 | 6/30/2005 | P | PASS |
Troy Cobbley
|
|
|
Hydro test for dry system #1 and #2 overhead systems and the two east branchlines under the canopy passed.
|
CHANGE STATUS TO (ISS) | | | 6/29/2005 | | DONE |
|
|
|
|
(F) Reprint permit | | | 6/29/2005 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in | 6/23/2005 | 6/24/2005 | 6/24/2005 | P | PART |
Forrest France
|
|
|
Overhead main piping is good for cover except at trapeze nw side sheet fp2 where retaining strap is not attatched and at three locations where 4" main passes through block wall without proper seismic clearance. Also, exposed branch lines on roof must meet req. of NFPA 13 8.15.3.2.3.
|
Plan assigned to (Bill) | 6/24/2005 | | 6/24/2005 | | PASS |
Bill Alexander
|
|
|
Reference requirements in revised REV2 comments attached.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/24/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 6/24/2005 | | DONE |
|
|
|
|
Telephone call | | | 6/24/2005 | | DONE |
|
|
|
tlk to steven johnson that permit and fees are ready to be picked up
|
Plan resubmittals received | | | 6/23/2005 | | |
|
|
|
|
INSP-Sprinkler Rough-in | 5/10/2005 | 5/12/2005 | 5/12/2005 | A | PART |
Troy Cobbley
|
|
|
The sprinkler piping for the exterior canopies is ok to cover. There is wood in areas above the ceiling in these exterior canopies. I notified the sprinkler contractor and the general contractor that this would have to be addressed since there are no upri
|
Sprinkler Plan Check | 5/12/2005 | | 5/12/2005 | | DONE |
Bill Alexander
|
|
|
A minor none system affecting 6" sprinkller main rerouting change.
|
Miscellaneous action | | | 5/12/2005 | | DONE |
|
|
|
Emailed approval and attached changes in a document, attached to this permit
|
INSP-Conference | 5/9/2005 | 5/10/2005 | 5/10/2005 | A | DONE |
Troy Cobbley
|
|
|
Looked at high canopy. It will require sprinkler coverage for concealed combustible space per NFPA 13 unless exceptions can be met
|
Issue and Print Permit | | | 5/4/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/26/2005 | | 4/26/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/26/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 4/14/2005 | | 4/25/2005 | | PASS |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 4/14/2005 | | 4/25/2005 | | DONE |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/25/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 4/14/2005 | | |
|
|
|
|
Sprinkler Plan Check | 3/29/2005 | | 3/29/2005 | | PASS |
Bill Alexander
|
|
|
Change in Contractor
|
Inspection Record Card- Fire | 3/29/2005 | | 3/29/2005 | | DONE |
|
|
|
|
Issue and Print Permit | | | 3/29/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 8/31/2004 | | 9/28/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/25/2004 | | 9/28/2004 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/28/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/28/2004 | | 9/28/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/28/2004 | | DONE |
|
|
|
|
Telephone call | | | 9/28/2004 | | DONE |
|
|
|
left mess for tom that permit is ready
|
Plan resubmittals received | | | 9/20/2004 | | |
|
|
|
|
Telephone call | | | 9/10/2004 | | DONE |
|
|
|
PLANS FAILED CALLED FOR PICK UP
|
Sprinkler Plan Check | 8/31/2004 | | 9/9/2004 | | FAIL |
Bill Alexander
|
|
|
The data has been moved to a Word document attached to this case.
|
Miscellaneous action | | | 9/9/2004 | | DONE |
|
|
|
Failed Plans taken to Permit Desk for calling and returning.
|
Application received | | | 8/31/2004 | | |
|
|
|
|