Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR04-00531
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 5100 W OVERLAND RD
Project NameSPR HILLCREST SHOPPING CENTER
Customer Number 
ePlanReview 
Description
HILLCREST SHOPPING CENTER - FIRE SPRINKLER UPGRADES * This permit is to install fire sprinkler protection in concealed combustible cavities and below ceilings of the outside canopy/soffit structures throughout this shopping center, where fire sprinkler protection is lacking. The fire sprinkler system work shall comply with the IFC 2000, attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is not attached to any other permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/5/20058/8/20058/8/2005APASS
DetailsTroy Cobbley
Fire sprinkler permit finaled
INSP-Final Inspection7/19/20057/20/20057/20/2005AFAIL
DetailsTroy Cobbley
Need to verify that the exposed combustibles located above the outside canopies has met requirements of NFPA 13 for combustible concealed spaces.
Sprinkler Plan Check7/5/2005 7/7/2005 PASS
DetailsBill Alexander
Changed compressor from a 30 gal 1HP K1S-30UMS to a 17gal 1HP K1S-BS due to system volume size.
Plan resubmittals received  7/5/2005  
INSP-Final Inspection6/29/20057/1/20057/1/2005APART
DetailsTroy Cobbley
Trip tested Dry System #1 and #2. Both sent in the correct alarm signals. Contractor still needs to correct overspaced and blocked heads under canopy, wrong air compressors installed, butterfly control valve on dry system #1 broke, need to blank off the switches controlling the air compressors, need to trip test the east dry system.
INSP-Sprinkler Rough-in/Hydro6/29/20056/30/20056/30/2005PPASS
DetailsTroy Cobbley
Hydro test for dry system #1 and #2 overhead systems and the two east branchlines under the canopy passed.
CHANGE STATUS TO (ISS)  6/29/2005 DONE
(F) Reprint permit  6/29/2005 DONE
INSP-Sprinkler Rough-in6/23/20056/24/20056/24/2005PPART
DetailsForrest France
Overhead main piping is good for cover except at trapeze nw side sheet fp2 where retaining strap is not attatched and at three locations where 4" main passes through block wall without proper seismic clearance. Also, exposed branch lines on roof must meet req. of NFPA 13 8.15.3.2.3.
Plan assigned to (Bill)6/24/2005 6/24/2005 PASS
DetailsBill Alexander
Reference requirements in revised REV2 comments attached.
PLANS/APPL TAKEN TO FRONT DESK  6/24/2005 DONE
Permit Ready to Issue  6/24/2005 DONE
Telephone call  6/24/2005 DONE
tlk to steven johnson that permit and fees are ready to be picked up
Plan resubmittals received  6/23/2005  
INSP-Sprinkler Rough-in5/10/20055/12/20055/12/2005APART
DetailsTroy Cobbley
The sprinkler piping for the exterior canopies is ok to cover. There is wood in areas above the ceiling in these exterior canopies. I notified the sprinkler contractor and the general contractor that this would have to be addressed since there are no upri
Sprinkler Plan Check5/12/2005 5/12/2005 DONE
DetailsBill Alexander
A minor none system affecting 6" sprinkller main rerouting change.
Miscellaneous action  5/12/2005 DONE
Emailed approval and attached changes in a document, attached to this permit
INSP-Conference5/9/20055/10/20055/10/2005ADONE
DetailsTroy Cobbley
Looked at high canopy. It will require sprinkler coverage for concealed combustible space per NFPA 13 unless exceptions can be met
Issue and Print Permit  5/4/2005 DONE
Inspection Record Card- Fire4/26/2005 4/26/2005 DONE
Permit Ready to Issue  4/26/2005 DONE
Sprinkler Plan Check4/14/2005 4/25/2005 PASS
DetailsBill Alexander
Plan assigned to (Bill)4/14/2005 4/25/2005 DONE
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  4/25/2005 DONE
Plan resubmittals received  4/14/2005  
Sprinkler Plan Check3/29/2005 3/29/2005 PASS
DetailsBill Alexander
Change in Contractor
Inspection Record Card- Fire3/29/2005 3/29/2005 DONE
Issue and Print Permit  3/29/2005 DONE
Plan assigned to (Bill)8/31/2004 9/28/2004 DONE
Sprinkler Plan Check9/25/2004 9/28/2004 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  9/28/2004 DONE
Inspection Record Card- Fire9/28/2004 9/28/2004 DONE
Permit Ready to Issue  9/28/2004 DONE
Telephone call  9/28/2004 DONE
left mess for tom that permit is ready
Plan resubmittals received  9/20/2004  
Telephone call  9/10/2004 DONE
PLANS FAILED CALLED FOR PICK UP
Sprinkler Plan Check8/31/2004 9/9/2004 FAIL
DetailsBill Alexander
The data has been moved to a Word document attached to this case.
Miscellaneous action  9/9/2004 DONE
Failed Plans taken to Permit Desk for calling and returning.
Application received  8/31/2004