Information based on query as of Sunday, September 27, 2026.
Permit Information
Permit NumberFIR04-00552
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 4444 W GINZEL ST
Project NameSPR WALLACE RESIDENCE
Customer Number 
ePlanReview 
Description
WALLACE RESIDENCE-SLEIGHT CONSTRUCTION, INC. * To construct install an NFPA 13D (modified) fire sprinkler system in a new 3,174-ft/2, three story single family dwelling. Modified relates to fire sprinkler protection along common walls and ceilings of occupied residential living space. Any and all NFPA 13D systems shall be equipped with an alarm initiating device, commonly referred to as a flow switch and an outside annunciating device. The lower level is: 812-ft/2; the main level is: 2,022ft/2 an upper level is: 340ft/2. All fire sprinkler work including a duel service underground supply and related, including the fire sprinkler system backflow prevention device (to be provided by others), shall be per NFPA 13D, plans, documents, engineered/red-lined plans and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD04-01262.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/13/20054/14/20054/14/2005APASS
DetailsTroy Cobbley
Fire sprinkler finaled
PLANS/APPL TAKEN TO FRONT DESK  4/13/2005 DONE
Inspection Record Card- Fire4/13/2005 4/13/2005 DONE
Issue and Print Permit  4/13/2005 DONE
Plan assigned to (Bill)3/30/2005 4/13/2005 DONE
DetailsBill Alexander
Telephone call  4/7/2005 DONE
tlk to receptionist to picked up fire to be return to sender for corrections
Sprinkler Plan Check3/30/2005 4/6/2005 PASS
DetailsBill Alexander
INSP-Final Inspection3/24/20053/28/20053/28/2005PFAIL
DetailsTroy Cobbley
Water meter is the wrong size, two pendants in the basement are too close to soffits. Still need to do all of the final signoff items. 3/28/2005 12:11:28 PM
INSP-Final Inspection3/15/20053/17/20053/17/2005ACANC
DetailsTroy Cobbley
Per Chris a dry sidewall has been broken. Inspection to be rescheduled. 3/17/2005 10:38:35 AM
INSP-Supply line flush3/1/20053/4/20053/4/2005APASS
DetailsTroy Cobbley
Underground flush ok 3/4/2005 1:11:28 PM
INSP-Sprinkler Rough-in/Hydro12/20/200412/20/200412/20/2004APASS
DetailsTroy Cobbley
Sprinkler piping in the entry and main corridor is ok to cover
INSP-Sprinkler Rough-in12/13/200412/14/200412/14/2004APART
DetailsTroy Cobbley
Sprinkler rough-in is passed for the overhead system. Underground has not been verified. Tenting is ok except for the entry/central corridor area which was not complete yet. 12/14/2004 11:40:02 AM
Telephone call  10/26/2004 DONE
left mess that permit is ready
Miscellaneous action  10/22/2004 DONE
Approved plans forwarded to the permit desk for calling and returning. (No Fee)
Plan resubmittals received  10/12/2004 DONE
Issue permit  9/28/2004  
Inspection Record Card- Fire9/21/2004 9/21/2004 DONE
Permit Ready to Issue  9/21/2004 DONE
Telephone call  9/21/2004 DONE
left mess that permit is ready
Plan assigned to (Bill)9/8/2004 9/20/2004 DONE
Sprinkler Plan Check9/8/2004 9/20/2004 PART
DetailsBill Alexander
1. Provide information addressing the "Upper Level" which occupies a 340-ft/2. If this space is above the garage, the areas below that living space must also be protected. (IFC 105.4.2, 901.2)
2. Provide current manufacturer fire sprinkler head data sheets with the correct head incorporating identified. (IFC 105.4.2, 901.2)
3. United Water uses the Neptune T10 model. Provide the size on the plans. (IFC 105.4.2, 901.2)
4. Calculation sheet "Page 1" does not identify the 12 lb friction loss/s. (IFC 105.4.2, 901.2)
5. Calculations address a 1 foot drop from the road tap to the meter and then a 5'-0" elevation lift to the face of floor (house). (IFC 105.4.2, 901.2)
6. Riser is located in the garage and heads protecting the same are Dry Sidewall sprinklers? Clarify how the riser will be protected from freeze damage. (IFC 105.4.2, 901.2)
7. Provide clarification of the two sprinklers and copper piping located on each end of the "Entry." Is this area subject to damage (freezing) above the ceiling? What does it mean the piping cannot be in the walls due to freezing and the piping is located at the ceiling? (IFC 105.4.2, 901.2)
PLANS/APPL TAKEN TO FRONT DESK  9/20/2004 DONE
DetailsBill Alexander
Application received  9/8/2004