Permit Information
Permit NumberFIR04-00554
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 500 W BROAD ST
Project NameSPR UG OAAS LANEY BLDG
Customer Number 
ePlanReview 
Description
(OAAS LANEY BLDG)(PHASE 2 - SHELL & CORE) To install approximately 90'-0" of 6" C-900 PVC underground pipe from the property line in W. Broad Street, north into a room located off the entrance and up through the floor with ductile. This work is for a new fire sprinkler system. This building will be fully fire sprinklered. The fire sprinkler underground supply main work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD04-01386.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  7/30/2010  
INSP-Final Inspection12/7/200412/7/200412/7/2004PPASS
DetailsRick Jackson
UG flush and hydro okay - final okay 12/7/2004 3:38:09 PM
DOC - Permit Finaled12/7/200412/7/200412/7/2004PPASS
DetailsRick Jackson
Finaled by inspector at 12/7/2004 3:38:11 PM
INSP-Final Inspection10/21/200410/22/200410/22/2004APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 10/21/2004 at 12:49:53 PM. Contact: ###-####. 2 layers of hard foam used over section of UG near steps; okay to cover 10/22/2004 9:40:36 AM
Plan assigned to (Bill)9/30/2004 10/21/2004 DONE
DetailsBill Alexander
Plan resubmittals received  10/21/2004  
DetailsBill Alexander
Sprinkler Plan Check10/21/2004 10/21/2004 PASS
DetailsBill Alexander
From: Bill Alexander
To: Stenquist, Ron
Date: 10/21/2004 12:21:45 PM
Subject: Re: OAAS Laney Bldg. Phase 2 Shell & Core (FIR04 00554)

This is approved on condition of a recommendation based on similar past installation issues and not a design acceptance of responsibility for any possible failure nor or in the future, in not meeting minimum installation code requirements as established by NFPA 13 and 24 (2000), by the installer. This is in no case an acceptance in practice for any other similar installation situations in meeting minimum code requirement.

Ron Stenquist" 10/21/2004 11:36:02 AM >>>
Dear Bill,

This email is sent in accordance with our telephone conversation this
morning regarding the insulation layer to be utilized to make up for the
approximately 6 inches of fill needed to meet NFPA 24 requirements for depth
of bury for private fire service mains.

Treasure Valley Fire Protection will install 2 inches of rigid insulation as
requested in your email dated October 11, 2004, in lieu of the proposed
therma cel flexible sheet insulation. This rigid insulation will be
installed today, by George Edes. TVFP requests that Rick Jackson inspects
this installation as soon as possible, so that the General Contractor can
proceed with the backfill process.

Thank you for your consideration and input in arriving at this solution.

Ron Stenquist
President
Treasure Valley Fire Protection,Inc
rons@tvfp.net
ph: 208 362 1888
fax: 208 362 2207




Bill Alexander
Fire Plans Examiner
City of Boise PDS/FD
Phone: (208) 395 7813
Cell: (208) 794 9469
Fax: (208) 388 4735
Issue and Print Permit  10/21/2004 DONE
Sprinkler Plan Check9/30/2004 10/11/2004 FAIL
DetailsBill Alexander
Revised underground layout and alternative request for depth of cover.
INSP-Sprinkler Rough-in/Hydro10/1/200410/1/200410/1/2004PNR
DetailsRick Jackson
Scheduled by a contractor via Hello! on 10/1/2004 at 10:35:42 AM. Contact: ###-####. Will reschedule 10/1/2004 4:14:17 PM
Plan resubmittals received  9/30/2004 DONE
INSP-Sprinkler Rough-in/Hydro9/27/20049/27/20049/27/2004PFAIL
DetailsRick Jackson
sam; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Resubmit due to changes; depth of bury won't be 4 ft 6 inches at present location 9/27/2004 4:29:28 PM
Issue and Print Permit  9/16/2004 DONE
Plan assigned to (Bill)9/8/2004 9/10/2004 DONE
Sprinkler Plan Check9/8/2004 9/10/2004 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  9/10/2004 DONE
Inspection Record Card- Fire9/10/2004 9/10/2004 DONE
Permit Ready to Issue  9/10/2004 DONE
Application received  9/8/2004