INSP-Sprinkler Rough-in/Hydro | 9/24/2004 | 9/27/2004 | 9/27/2004 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/24/2004 at 11:48:04 AM. Contact: ###-####. Minor changes made to line from hall to kitchen 9/27/2004 11:52:57 AM
|
DOC - Permit Finaled | 9/27/2004 | 9/27/2004 | 9/27/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 9/27/2004 11:53:02 AM
|
Sprinkler Plan Check | 9/27/2004 | | 9/27/2004 | | PASS |
Bill Alexander
|
|
|
Revised sprinkler head from standard Q.R. to Residential per head correction requirement.
|
Plan assigned to (Bill) | 9/24/2004 | | 9/27/2004 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/27/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/27/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/27/2004 | | 9/27/2004 | | DONE |
|
|
|
|
Telephone call | | | 9/27/2004 | | DONE |
|
|
|
Spoke with Jeff and told him that permit is ready & fees///9/27/04 BAS
|
(F) Reprint permit | | | 9/27/2004 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 9/27/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/24/2004 | | DONE |
Bill Alexander
|
|
|
|
Issue permit | | | 9/20/2004 | | |
|
|
|
|
Plan assigned to (Bill) | 9/9/2004 | | 9/17/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/16/2004 | | 9/17/2004 | | PASS |
Bill Alexander
|
|
|
With Conditions
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/17/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/17/2004 | | 9/17/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/16/2004 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 9/9/2004 | | 9/13/2004 | | FAIL |
Bill Alexander
|
|
|
1. The (original) calculation design plate (which is also nearly impossible to read) appears to have the wrong protection design for the occupancy use required in this facility. This facility is an R-2, two stories and requires a protection design meeting NFPA 13R, not a 13D as so indicated and addressed (scope of work). Provide clarification that this facility is currently designed for a 13R. It also appears that the original system is incorporating standard heads installed in a manor which exceeds their listing? If this is the case and the system requires corrections meeting a code upgrade; obtain an Upgrade Agreement which is approved by Boise City Fire Marshal, Dave Miller. (IFC 903.2.8)
2. Six sprinkler heads are addressed in this submittal, but none are identified specifically to which the designer is incorporating. When submitting documents with multiple choices, identify each of the item/s incorporating. (IFC 105.4, 901.2)
3. Clarify the exposed CPVC piping is and will be installed in accordance with its listing and that it meets the manufacturer's installation instruction requirements for "Exposed Installations."
|
Miscellaneous action | | | 9/13/2004 | | DONE |
|
|
|
Failed plans/documents taken to "Permit Desk" for returning.
|
Telephone call | | | 9/13/2004 | | DONE |
|
|
|
plans failed called for pick up
|
Application received | | | 9/9/2004 | | |
|
|
|
|