INSP-Sprinkler Rough-in/Hydro | 9/27/2004 | 9/27/2004 | 9/27/2004 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/27/2004 at 9:59:38 AM. Contact: ###-####.
|
DOC - Permit Finaled | 9/27/2004 | 9/27/2004 | 9/27/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 9/27/2004 2:25:13 PM
|
Issue permit | | | 9/24/2004 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/23/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/23/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/23/2004 | | 9/23/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/23/2004 | | DONE |
|
|
|
|
Telephone call | | | 9/23/2004 | | DONE |
|
|
|
left mess that permit is ready
|
Plan assigned to (Bill) | 9/9/2004 | | 9/23/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/22/2004 | | 9/23/2004 | | PASS |
Bill Alexander
|
|
|
|
Plan resubmittals received | | | 9/22/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/16/2004 | | 9/16/2004 | | FAIL |
Bill Alexander
|
|
|
Called Designer Brodie Stenquist and indicated that I could not accept his resubmittal since he gives no information on the existing piping, i.e., gridded or tree. Need verification that it is gridded.
|
Plan resubmittals received | | | 9/15/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/9/2004 | | 9/13/2004 | | FAIL |
Bill Alexander
|
|
|
1. This area use is defined as a "Laboratory." Laboratories shall be protected per requirements of NFPA 13:13.8 which addresses NFPA 45, "Standard on Fire Protection for Laboratories Using Chemicals", of which, (1) Automatic sprinkler system protection for Class A and Class B laboratories shall be in accordance with ordinary hazard, Group 2 occupancies OR (2) Automatic sprinkler system protection for Class C and Class D laboratories shall be in accordance with ordinary hazard, Group 1 occupancies. [NFPA 45:4.2.1.1] Provide correct occupancy use definition of laboratory protecting and include corrected plans verifying the area is protected per minimum density/area requirements for that identified lab type. (IFC 105.4, 901.2)
|
Miscellaneous action | | | 9/13/2004 | | DONE |
|
|
|
Failed plans and documents taken to "Permit Desk" for returning.
|
Telephone call | | | 9/13/2004 | | DONE |
|
|
|
permit failed called for pick up
|
Application received | | | 9/9/2004 | | |
|
|
|
|