Permit Information
Permit NumberFIR04-00558
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 190 E BANNOCK ST
Project NameSPR SLRMC-1E MICROBIOLOGY LAB
Customer Number 
ePlanReview 
Description
(ST LUKES- 1E MICROBIOLOGY LAB) To relocate 11 existing recessed and add 7 pendant fire sprinklers within a 1,100-ft/2 area of existing medical process laboratory. Fire sprinkler work is associated with the upgrade use of a Microbiology Lab, by constructing new interior non-bearing partitions to create work stations and areas as necessary to meet tenant needs which shall comply with current adopted codes and ordinances. This fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-01070.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in/Hydro9/27/20049/27/20049/27/2004PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 9/27/2004 at 9:59:38 AM. Contact: ###-####.
DOC - Permit Finaled9/27/20049/27/20049/27/2004PPASS
DetailsRick Jackson
Finaled by inspector at 9/27/2004 2:25:13 PM
Issue permit  9/24/2004 DONE
PLANS/APPL TAKEN TO FRONT DESK  9/23/2004 DONE
Plan resubmittals received  9/23/2004 DONE
Inspection Record Card- Fire9/23/2004 9/23/2004 DONE
Permit Ready to Issue  9/23/2004 DONE
Telephone call  9/23/2004 DONE
left mess that permit is ready
Plan assigned to (Bill)9/9/2004 9/23/2004 DONE
Sprinkler Plan Check9/22/2004 9/23/2004 PASS
DetailsBill Alexander
Plan resubmittals received  9/22/2004 DONE
Sprinkler Plan Check9/16/2004 9/16/2004 FAIL
DetailsBill Alexander
Called Designer Brodie Stenquist and indicated that I could not accept his resubmittal since he gives no information on the existing piping, i.e., gridded or tree. Need verification that it is gridded.
Plan resubmittals received  9/15/2004 DONE
Sprinkler Plan Check9/9/2004 9/13/2004 FAIL
DetailsBill Alexander
1. This area use is defined as a "Laboratory." Laboratories shall be protected per requirements of NFPA 13:13.8 which addresses NFPA 45, "Standard on Fire Protection for Laboratories Using Chemicals", of which, (1) Automatic sprinkler system protection for Class A and Class B laboratories shall be in accordance with ordinary hazard, Group 2 occupancies OR (2) Automatic sprinkler system protection for Class C and Class D laboratories shall be in accordance with ordinary hazard, Group 1 occupancies. [NFPA 45:4.2.1.1] Provide correct occupancy use definition of laboratory protecting and include corrected plans verifying the area is protected per minimum density/area requirements for that identified lab type. (IFC 105.4, 901.2)
Miscellaneous action  9/13/2004 DONE
Failed plans and documents taken to "Permit Desk" for returning.
Telephone call  9/13/2004 DONE
permit failed called for pick up
Application received  9/9/2004