INSP-Final Inspection | 1/13/2005 | 1/14/2005 | 1/14/2005 | A | PASS |
Troy Cobbley
|
|
|
Contact: Chris - Would like to have inspection done around 10 AM Please.; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
|
DOC - Permit Finaled | 1/14/2005 | 1/14/2005 | 1/14/2005 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 1/14/2005 10:48:57 AM
|
INSP-Final Inspection | 1/12/2005 | 1/13/2005 | 1/13/2005 | A | FAIL |
Troy Cobbley
|
|
|
contractor did not arrive for inspection 1/13/2005 10:13:42 AM
|
INSP-Sprinkler Rough-in/Hydro | 1/12/2005 | 1/13/2005 | 1/12/2005 | A | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
INSP-Final Inspection | 10/13/2004 | 10/13/2004 | 10/13/2004 | P | FAIL |
Troy Cobbley
|
|
|
Fire sprinklers are not ready for a final but the piping is ok to cover. The water meter sizing has not been addressed 10/13/2004 12:35:57 PM
|
INSP-Final Inspection | 10/11/2004 | 10/12/2004 | 10/12/2004 | P | PART |
Troy Cobbley
|
|
|
sprinkler piping is ok to cover except for pantry which sprinkler pendant was missed. 10/12/2004 4:49:35 PM
|
INSP-Final Inspection | 10/8/2004 | 10/11/2004 | 10/11/2004 | A | FAIL |
Troy Cobbley
|
|
|
No approved plans on site and sprinkler piping is cover with sheet rock. There is no access for inspection of piping or tenting. 10/11/2004 10:11:08 AM
|
Sprinkler Plan Check | 9/28/2004 | | 10/8/2004 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/8/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/8/2004 | | |
|
|
|
|
Inspection Record Card- Fire | 10/8/2004 | | 10/8/2004 | | DONE |
|
|
|
|
Telephone call | | | 10/8/2004 | | DONE |
|
|
|
left mess that permit is ready
|
Issue permit | | | 10/8/2004 | | DONE |
|
|
|
|
INSP-Conference | 10/5/2004 | 10/5/2004 | 10/5/2004 | A | DONE |
Troy Cobbley
|
|
|
The building contractor called to let me know that the sheet rockers had begun to install sheet rock on the ceiling and that he was letting them know that it was to be removed since no inspection had been done on the sprinkler piping. He let me know this in case I happen to show up before the sheet rock had been removed.
|
Plan assigned to (Bill) | 9/28/2004 | | 10/1/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/28/2004 | | |
|
|
|
|
Telephone call | | | 9/23/2004 | | DONE |
|
|
|
left vm with john regarding fail fire sprinkler to be picked up
|
Plan assigned to (Bill) | 9/13/2004 | | 9/21/2004 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/21/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/13/2004 | | 9/21/2004 | | FAIL |
Bill Alexander
|
|
|
1. The ¾" Neptune water meter is not listed for calculation loss of 60+ gpm flow as established through the garage protection. Revise and resubmit. (IFC 105.4.2, 901.2)
2. Calculation sheets "Page 1" does not identify the friction loss/s addressing. Meter, Residential Domestic Shutoff and Backflow Preventer should all be addressed. Provide clarifications. (IFC 105.4.2, 901.2)
3. Provide current manufacturer fire sprinkler head data sheets (including all pages) with the correct head/s incorporating identified. (IFC 105.4.2, 901.2)
4. Riser is located in the garage and heads protecting the same are Dry Sidewall sprinklers? Clarify how the riser will be protected from freeze damage. (IFC 105.4.2, 901.2)
|
Application received | | | 9/13/2004 | | |
|
|
|
|
INSP-Conference | 9/1/2004 | 9/1/2004 | 9/1/2004 | P | DONE |
Troy Cobbley
|
|
|
Building contractor called wanting to know if I could do anything to speed up the review. I told him no and relayed the job history to him such as review and resubmittal dates to him.
|