Permit Information
Permit NumberFIR04-00561
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 4148 W QUAIL HILL CT
Project NameSPR DUTTON RESIDENCE
Customer Number 
ePlanReview 
Description
DUTON RESIDENCE * To construct install an NFPA 13D (modified) fire sprinkler system in a new 2,933-ft/2 one story single family dwelling with a 879-ft/2 attached three car garage single family dwelling. Modified relates to fire sprinkler protection along common walls and ceilings of occupied residential living space. Any and all NFPA 13D systems shall be equipped with an alarm initiating device, commonly referred to as a flow switch and an outside alarm indicating device. All fire sprinkler work including a duel service underground supply and related, including the fire sprinkler system backflow prevention device (to be provided by others), shall be per NFPA 13D, plans, documents, engineered/red-lined plans and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD04-01472.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/13/20051/14/20051/14/2005APASS
DetailsTroy Cobbley
Contact: Chris - Would like to have inspection done around 10 AM Please.; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
DOC - Permit Finaled1/14/20051/14/20051/14/2005APASS
DetailsTroy Cobbley
Finaled by inspector at 1/14/2005 10:48:57 AM
INSP-Final Inspection1/12/20051/13/20051/13/2005AFAIL
DetailsTroy Cobbley
contractor did not arrive for inspection 1/13/2005 10:13:42 AM
INSP-Sprinkler Rough-in/Hydro1/12/20051/13/20051/12/2005ACANC
DetailsTroy Cobbley
Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
INSP-Final Inspection10/13/200410/13/200410/13/2004PFAIL
DetailsTroy Cobbley
Fire sprinklers are not ready for a final but the piping is ok to cover. The water meter sizing has not been addressed 10/13/2004 12:35:57 PM
INSP-Final Inspection10/11/200410/12/200410/12/2004PPART
DetailsTroy Cobbley
sprinkler piping is ok to cover except for pantry which sprinkler pendant was missed. 10/12/2004 4:49:35 PM
INSP-Final Inspection10/8/200410/11/200410/11/2004AFAIL
DetailsTroy Cobbley
No approved plans on site and sprinkler piping is cover with sheet rock. There is no access for inspection of piping or tenting. 10/11/2004 10:11:08 AM
Sprinkler Plan Check9/28/2004 10/8/2004 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  10/8/2004 DONE
Permit Ready to Issue  10/8/2004  
Inspection Record Card- Fire10/8/2004 10/8/2004 DONE
Telephone call  10/8/2004 DONE
left mess that permit is ready
Issue permit  10/8/2004 DONE
INSP-Conference10/5/200410/5/200410/5/2004ADONE
DetailsTroy Cobbley
The building contractor called to let me know that the sheet rockers had begun to install sheet rock on the ceiling and that he was letting them know that it was to be removed since no inspection had been done on the sprinkler piping. He let me know this in case I happen to show up before the sheet rock had been removed.
Plan assigned to (Bill)9/28/2004 10/1/2004 DONE
Plan resubmittals received  9/28/2004  
Telephone call  9/23/2004 DONE
left vm with john regarding fail fire sprinkler to be picked up
Plan assigned to (Bill)9/13/2004 9/21/2004 DONE
PLANS/APPL TAKEN TO FRONT DESK  9/21/2004 DONE
Sprinkler Plan Check9/13/2004 9/21/2004 FAIL
DetailsBill Alexander
1. The ¾" Neptune water meter is not listed for calculation loss of 60+ gpm flow as established through the garage protection. Revise and resubmit. (IFC 105.4.2, 901.2)
2. Calculation sheets "Page 1" does not identify the friction loss/s addressing. Meter, Residential Domestic Shutoff and Backflow Preventer should all be addressed. Provide clarifications. (IFC 105.4.2, 901.2)
3. Provide current manufacturer fire sprinkler head data sheets (including all pages) with the correct head/s incorporating identified. (IFC 105.4.2, 901.2)
4. Riser is located in the garage and heads protecting the same are Dry Sidewall sprinklers? Clarify how the riser will be protected from freeze damage. (IFC 105.4.2, 901.2)
Application received  9/13/2004  
INSP-Conference9/1/20049/1/20049/1/2004PDONE
DetailsTroy Cobbley
Building contractor called wanting to know if I could do anything to speed up the review. I told him no and relayed the job history to him such as review and resubmittal dates to him.