Permit NumberFIR04-00575
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 802 W BANNOCK ST
Project Namealm - HOFF BUILDING-7TH FLR
Customer NumberHIGHWAY 12
ePlanReview 
Description
To provide required area smoke detection and notification (speaker/strobes) on the entire 7th floor. The core area was upgraded previously and existing devices/appliances are shown on the plans. The required manual fire alarm system includes required automatic detection, HVAC shutdown, fire/smoke damper control, door release and notification (speaker/strobes) throughout.

1/13/2005 - Plan Modification was submitted by request of PDS Fire Inspector, per an inspection/Notice of Violation (dated 11/29/2004) that addresses (initiating devices) and the NAC circuit were not installed per approved FA permitted plans. This Plan Modification is the as-built of the 7th floor.

The associated building permit (BLD 04-01093) is to remodel a 1,488 square foot area on the 7th floor of the Hoff Building for a new office occupant. This tenant will occupy about half of the floor. Work is to include interior nonbearing walls, interior doors, and interior windows all per the approved drawings and the plan review report on file. A total coverage smoke detection fire alarm system will be installed throughout the 7th floor in lieu of exit separation. If smoke is detected anywhere on the 7th floor, the entire 7th floor shall be alarmed. A separate alarm permit is required. Within the modified areas, fire sprinkler heads shall be located or relocated to comply with NFPA 13-2002 as regulated by the Fire Department. **CJW** HIGHWAY 12 - HOFF BUILDING - 7TH FLR) This building is fire sprinklered for building area increase, because it is a high-rise, and to comply with 1994 UCBC provisions.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/19/20051/20/20051/20/2005APASS
DetailsRick Jackson
Rick, We spoke to the Hoff Building Maintenance man Kevin. He would like to test at 10:00am tomorrow if at all possible. He will notify everyone in the building tonight, so that they may plan ahead. If there is a problem with that time, please let me know as soon as possible, so that we may let the building occupants know when to expect a test. My cell number is ###-#### if you cannot reach me at the office. Thank you for your time. Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick
DOC - Permit Finaled1/20/20051/20/20051/20/2005APASS
DetailsRick Jackson
Finaled by inspector at 1/20/2005 10:46:27 AM
INSP-Final Inspection1/17/20051/18/20051/18/2005PFAIL
DetailsRick Jackson
Rick, We would like to have you come out and check off the violations from your prior inspection. Wendy at the Hoff Building is off on vacation, but asked if we could request that you bring Dave Hanna along as well to sign off on their structural as well. Please call me at the office (###-####), or on my cell (###-####) when you know when would be a good time. Thank you for your time. jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick All other tiems completed except the volume of the voice page is barely audible 1/18/2005 2:19:26 PM
Issue and Print Permit  1/14/2005 DONE
Alarm Plan Check  1/13/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  1/13/2005 DONE
Permit Ready to Issue  1/13/2005 DONE
Inspection Record Card- Fire1/13/2005 1/13/2005 DONE
Telephone call  1/13/2005 DONE
Spoke with Mike and told him that permit is ready with no fees///1/13/05 3:05pm BAS
Plan resubmittals received  1/7/2005 DONE
INSP-Final Inspection11/22/200411/29/200411/29/2004AFAIL
DetailsRick Jackson
Rick, We would like to request meeting at the Hoff building at 9:00am if possible. Please advise us if there is a better time for you. You can reach me here at the office, or on my cell phone at ###-#### as needed. Thank you. Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick FACP panel displat not operating; voice page does not tell occupants to exit but to wait at corridors; initiating devices don't match plan addresses; all page microphone not working; BPS one-line diagrams don't match actual wiring; need updated maps 11/29/2004 11:41:38 AM
Issue and Print Permit  9/23/2004  
Plan assigned to (Mary)9/17/2004 9/22/2004 DONE
Alarm Plan Check  9/22/2004 PASS
Approved pending field inspection of fire alarm permit comments.
Telephone call  9/22/2004 DONE
Spoke to Jason Minnick, requested wattage calculations for the VEC.
Plan resubmittals received  9/22/2004 DONE
Received the VEC wattage calculations via e-mail.
PLANS/APPL TAKEN TO FRONT DESK  9/22/2004 DONE
Inspection Record Card- Fire9/22/2004 9/22/2004 DONE
Permit Ready to Issue  9/22/2004 DONE
Telephone call  9/22/2004 DONE
left mess that permit is ready
Application received  9/17/2004