INSP-Final Inspection | 1/26/2005 | 1/26/2005 | 1/26/2005 | P | PASS |
Troy Cobbley
|
|
|
fire sprinkler finaled 1/26/2005 4:48:38 PM
|
DOC - Permit Finaled | 1/26/2005 | 1/26/2005 | 1/26/2005 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 1/26/2005 4:49:04 PM
|
INSP-Sprinkler Rough-in/Hydro | 1/20/2005 | 1/20/2005 | 1/20/2005 | P | PART |
Troy Cobbley
|
|
|
Forward flush was ok. Need to provide valve for lower guage, test papers and certification for the backflow preventer. 1/20/2005 12:06:50 PM
|
INSP-Sprinkler Rough-in | 1/19/2005 | 1/19/2005 | 1/19/2005 | P | PASS |
Troy Cobbley
|
|
|
Sprinkler piping matches the resubmitted plans. 1/19/2005 1:24:46 PM
|
Issue and Print Permit | | | 1/19/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 1/13/2005 | | 1/14/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 1/13/2005 | | 1/14/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/14/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/14/2005 | | 1/14/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/14/2005 | | DONE |
|
|
|
|
Telephone call | | | 1/14/2005 | | DONE |
|
|
|
lft mes with sec ###-#### that permit and fees are ready to be picked up
|
Plan resubmittals received | | | 1/13/2005 | | |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 1/11/2005 | 1/12/2005 | 1/12/2005 | P | PART |
Troy Cobbley
|
|
|
Overhead hydro test ok. Plans need to be resubmitted. Both mains are installed closer to the center of the building than shown on the plans and the tail backs are 2" instead of 1". Main out of riser room has also been rerouted. The branchline along the north wall is approx. 7'-2" off of the wall. Plans show 5'-11" 1/12/2005 12:40:29 PM
|
FIR-Aging Inspection | 1/4/2005 | 1/4/2005 | 1/4/2005 | | NR |
Troy Cobbley
|
|
|
|
Issue permit | | | 10/5/2004 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 9/22/2004 | | 10/4/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/22/2004 | | 10/4/2004 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/4/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/4/2004 | | 10/4/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/4/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/4/2004 | | 10/4/2004 | | DONE |
|
|
|
|
Telephone call | | | 10/4/2004 | | DONE |
|
|
|
Left message for Don with Melody that permit is ready & fees///12:34pm 10/04/04 BAS
|
Application received | | | 9/22/2004 | | |
|
|
|
|