Permit Information
Permit NumberFIR04-00592
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 5598 N QUAIL SUMMIT PL
Project NameSPR WILLIAM KEOUGH RES
Customer Number 
ePlanReview 
Description
WILLIAM KEOUGH RESIDENCE * To install an NFPA 13D (Modified) fire sprinkler system which includes fire sprinkler barrier protection between garage and dwelling in a 3,495-ft/2 one story single family dwelling with a 528-ft/2 attached two car garage. This NFPA 13D systems shall be equipped with an alarm initiating device, commonly referred to as a flow switch connected to an outside alarm device. All fire sprinkler work and related, which includes dual use, single service water supply and system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD04-01201.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  3/11/2005 DONE
INSP-Final Inspection3/2/20053/2/20053/2/2005PPASS
DetailsTroy Cobbley
Fire sprinkler finaled 3/2/2005 4:50:05 PM
DOC - Permit Finaled3/2/20053/2/20053/2/2005PPASS
DetailsTroy Cobbley
Finaled by inspector at 3/2/2005 4:50:09 PM
INSP-Final Inspection2/24/20052/25/20052/25/2005AFAIL
DetailsTroy Cobbley
John; Phone #: ###-#### Internet Inspection Request from: Jan Rice

U.G. Flush OK
Failed:
1. 3/4" meter installed, (requires 1" per calcs).
2. Inspectors test failed. Line malfunction (cracked 1/2" adapter).
Case Summary  2/24/2005 DONE
INSP-Sprinkler Rough-in10/28/200410/29/200410/29/2004APART
DetailsTroy Cobbley
Inspection was for overhead sprinkler roughing and tenting. Overhead sprinklers are ok to cover. Underground supply piping is ok except for the water meter is not the right size. Its 3/4" not 1" as required. 10/29/2004 1:59:13 PM
Issue and Print Permit  10/26/2004 DONE
Plan assigned to (Bill)9/27/2004 10/25/2004 DONE
Sprinkler Plan Check10/13/2004 10/25/2004 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  10/25/2004 DONE
Permit Ready to Issue  10/25/2004 DONE
Inspection Record Card- Fire10/25/2004 10/25/2004 DONE
Telephone call  10/13/2004 DONE
Spoke with secretary and left her a message that plans failed and need picked up///10/13/04 10:25am BAS
Plan resubmittals received  10/13/2004  
Sprinkler Plan Check9/27/2004 10/12/2004 FAIL
DetailsBill Alexander
1. It is assumed that the supply from the meter (node#1) to inside the house (node #2) does not travel uphill, since no elevation pressure loss was found in the calcs. If elevation exceeds 12 feet of lift, plan submittal is denied and resubmittal required. (IFC 105.4)
2. Bathroom and toilet off of Bedroom #1 (located in the northeast corner of the house) shall require lintel separation or fire sprinkler protection will be required (NFPA 13D:4.1.2)
3. Master Bath room has 2 toilets and an unidentified room space, which must be separated by an 8" minimum lintel or they shall included fire protection. (NFPA 13D:4.1.2)
4. All areas addressed shall require full and complete construction other than closets and bathrooms which meet the exceptions. Head located in "BRKFST" room is approximately 3'-0" from the "fireplace." No consideration provided in meeting requirements of NFPA 13D Table 7.5.5.3 or "RFC Residential Sprinkler Design and Installation Guide" page 5, Table B (not provided). (IFC 105.4)
5. Kitchen, Library and dining room appear to have continuous beam obstructions? Designer does not indicate in this submittal of whether meeting obstruction rule limits per 8.2.4* and head listing requirements "RFC Residential Sprinkler Design and Installation Guide" page 8, Figure 1, page 11, Figure 4 (document is not provided). (IFC 105.4)
6. Garage spacing of sidewall heads exceed listing (even though they have not been verified for meeting minimum spacing). Riser detail indicates an upright sprinkler, which is not shown on the floor plan. If this head is being installed, identify it in the head legend, provide data submittal and show it on your floor plan. (IFC 105.4)
7. A room south off the "Great Room" appears to have some sort of mechanical room/closet. Mechanical closet/rooms are not except from protection. If this is actually a mechanical room/closet, then include protection and address it in the head legend and submittal data. (IFC 105.4)
8. Provide clarification of ceiling changes and coverage for entry to the hallway to the garage from the kitchen. (IFC 105.4)
9. Provide clarification of ceiling changes in the "M CLST". (IFC 105.4)
10. Provide a fire sprinkler head box, wrench and minimum number of heads installing. (IFC 105.4)
11. Clarify underground supply line, (Plan FP-1) is flat and not on a rise with this foothill home, since the calculations address no change in elevation loss pressures from node 2 to 3.

Note: Riser detail (FP-1) needs corrections and/or clarification.
A. It is advisable to relocate domestic shutoff to the supply side of the sprinkler takeoff tee. This will meet requirements of 7.1.1, which provides supervision of the supply to fire sprinklers.
B. System control valve adding down stream of the backflow is not required. Backflow preventer shall have the valve handles installed, which shall be indicating per A.3.3.10.2 and supervised by one of the approved methods addressed in 7.1.2.
C. Remove verbiage addressing alarm interconnection requirements per NFPA 72:2-2.1.1.3 which not a current NFPA 72 paragraph.
D. Clarify supply from pump.
E. Clarify the riser will not have any exposed CPVC and if it does, then change the sprinkler head to meet minimum manufactures listing requirements for the same. (IFC 105.4)
Miscellaneous action  10/12/2004 DONE
Returned plans to permit desk for returning.
Application received  9/27/2004