Permit Information
Permit NumberFIR04-00595
StatusFinaled
Name SCOTT NORIYUKI (GC REP)
Site Address 7040 S EISENMAN RD
Project NameSPR VANITY FAIR
Customer Number 
ePlanReview 
Description
(VANITY FAIR - BOISE FACTORY OUTLETS - BLDG 4) To modify existing fire sprinkler protection system for the creation of a 25,860-ft/2 retail sales tenant space, located within an existing 32,400-ft/2 foot building, which will combine several smaller tenant spaces. Fire sprinkler work is related to the demolition of 2 existing shear walls and the installation new shear walls, the interior nonbearing walls, 2 restrooms and fitting rooms. This building is fire sprinklered for building area increase and for fire area. This fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-01860.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/28/200410/29/200410/29/2004AFAIL
DetailsRick Jackson
Steve; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner Janitor closet lacking sprinkler protection; heads overspaced (130 sq ft) in middle of sales floor as design is 120 sq ft; need spare heads in head box 10/29/2004 10:56:00 AM
INSP-Final Inspection10/29/200410/29/200410/29/2004PPASS
DetailsRick Jackson
DOC - Permit Finaled10/29/200410/29/200410/29/2004PPASS
DetailsRick Jackson
Finaled by inspector at 10/29/2004 4:18:55 PM
Permit Ready to Issue  10/13/2004 DONE
Inspection Record Card- Fire10/13/2004 10/13/2004 DONE
Telephone call  10/13/2004 DONE
Spoke with John and told him that the permit is ready & fees///10/13/04 BAS
Issue permit  10/13/2004 DONE
Plan assigned to (Bill)9/28/2004 10/12/2004 DONE
PLANS/APPL TAKEN TO FRONT DESK  10/12/2004 DONE
Sprinkler Plan Check9/28/2004 10/11/2004 PASS
DetailsBill Alexander
Application received  9/28/2004