Permit Information
Permit NumberFIR04-00597
StatusFinaled
Name NORTHWEST SALES COMPANY
Site Address 101 S CAPITOL BLVD Unit: 1900
Project Namealm - US BANK-18/19/2TH FLRS
Customer NumberSTOEL RIVES LLP
ePlanReview 
Description
To add A/V appliances for the TI remodels (floors 18, 19 and 20) to an existing required fire alarm system that includes manual pull stations, automatic detection, sprinkler monitoring, HVAC shutdown, elevator recall/shutdown, fire/smoke damper control, door release, high rise bldg requirements and notification appliances throughout.

The associated building permit (BLD 04-00029) is to expand an existing tenant space located on the 19th floor (11,626 square feet) and on the 20th floor (3,740 square feet) into the 18th floor (11,627 square feet). In addition to occupying a portion of the 20th floor and all of the 19th floor, this tenant will also occupy all of the 18th floor. All levels will be interconnected by interior stairways that are not part of the egress system. The restrooms located on the 18th floor and the restrooms located on the 19th floor will be upgraded to be accessible to the disabled. Work is to include interior nonbearing walls, a stairway located in a new floor opening between the 18th and 19th floor, a new stairway located in an existing floor opening between the 19th and 20th floor, interior nonbearing walls, interior windows, interior doors, millwork, suspended ceilings, gypsum board ceilings, and interior finishes all per the approved drawings and plan review report on file. The fire sprinkler system shall comply with NFPA 13-2002 as regulated by the Fire Department. **CJW** STOEL RIVES LLP - US BANK BLDG - 18th, 19th, & 20th FLOORS) This building is fire sprinklered because it is a high-rise.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Alarm Testing3/14/20053/15/20053/15/2005APASS
DetailsTroy Cobbley
Fire alarm finaled 3/15/2005 12:20:05 PM
DOC - Permit Finaled3/15/20053/15/20053/15/2005PPASS
DetailsTroy Cobbley
Finaled by inspector at 3/15/2005 12:20:09 PM
INSP-Alarm Testing3/10/20053/11/20053/11/2005PFAIL
DetailsTroy Cobbley
No approved plans. We did set off the a/v circuit and everything worked. 3/11/2005 3:52:22 PM
INSP-Alarm Testing11/22/200411/23/200411/23/2004APART
DetailsRick Jackson
Rick, give me a call so that I can set up a time with the bldg management. Thanks Internet Inspection Request from: Rick Groom Phased project - 18th floor only okay 11/23/2004 2:52:10 PM
Plan assigned to (Mary)9/29/2004 10/4/2004 DONE
Plan resubmittals received  10/4/2004 DONE
Received the voice/evac information via e-mail. 100 W amplifiers are located on the 2nd, 7th, 11th and 18th floor. The speaker calculations are included in the permit package.
Alarm Plan Check  10/4/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  10/4/2004 DONE
Inspection Record Card- Fire10/4/2004 10/4/2004 DONE
Permit Ready to Issue  10/4/2004 DONE
Telephone call  10/4/2004 DONE
Spoke with Rick and told him that permit is ready & fees///10/04/04 BAS
Issue and Print Permit  10/4/2004 DONE
Telephone call  10/1/2004 DONE
Request additional information on the voice/evac capacity. Left a message for Rick Groom.
Application received  9/29/2004