INSP-Final Inspection | 7/27/2005 | 7/27/2005 | 7/27/2005 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 11/29/2004 | 11/29/2004 | 11/29/2004 | P | PASS |
Troy Cobbley
|
|
|
Hydro test on the new antifreeze loop is ok. Sprinkler rough-in is ok. There are still items that need to be completed at the final such as forward flush and alarm connections. Piping size on plans as compared to hydraulic calculations does not match. Per bill alexander what has been installed is ok. 11/29/2004 3:09:18 PM
|
Issue and Print Permit | | | 10/27/2004 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 9/30/2004 | | 10/26/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 10/19/2004 | | 10/26/2004 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/26/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/26/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/26/2004 | | 10/26/2004 | | DONE |
|
|
|
|
Telephone call | | | 10/26/2004 | | DONE |
|
|
|
Left message that permit is ready & fees///10/26/04 4:00pm BAS
|
Plan resubmittals received | | | 10/19/2004 | | |
Bill Alexander
|
|
|
|
Telephone call | | | 10/14/2004 | | DONE |
|
|
|
Left message with Julie that plans failed and need picked up///10/14/04 8:25am BAS
|
Sprinkler Plan Check | 10/13/2004 | | 10/13/2004 | | FAIL |
Bill Alexander
|
|
|
1. The calculations provided do not verify that both backflow preventers were addressed completely? (Reference your calculation sheet #2). With the most demanding verified flow of 329-gpm required, the minimum pressure loss of 7+ lbs in the Ames Maxim and another 4 would be addressed in the risers Zurn Wilkins.
2. Designer shall include data submittals on the expansion chamber which shall be sized meeting an approved formula relating to the antifreeze systems capacity. A formula used and approved is addressed in A.7.5.3.2. (IFC 105.4)
|
Miscellaneous action | | | 10/13/2004 | | DONE |
|
|
|
Returned plans to the permit desk for returning and corrections.
|
Application received | | | 9/30/2004 | | |
|
|
|
|