Permit Information
Permit NumberFIR04-00605
StatusFinaled
Name ADT SECURITY SERVICES INC
Site Address 7000 W STATE ST
Project Namealm - NORTHGATE SHOP CENTER
Customer Number 
ePlanReview 
Description
To provide sprinkler monitoring fire alarm systems for the Northgate shopping center. The existing monitoring points will be removed from the ADT Focus 45 panel in the theater. This panel will continue to monitor the Simplex fire alarm system installed for the theater. Verification of the proper signals to the remote supervising monitoring station will be required after the demolition work has been completed.

A new addressable fire alarm panel will be installed in the riser room behind Brew's Brothers. This panel will monitor the sprinkler systems and duct detectors and cooking hoods for the east side of the complex. (From the east riser room to DBSI)

An existing Radionics panel (located in the Early Learning Pre-School) will be expanded to include the sprinkler monitoring for the building spaces between Albertsons and Rite-Aid.

Albertsons and Rite-Aid have their own fire alarm systems.

The associated building permit (BLD 04-01819) is to remodel a 34,069 sq.ft. tenant space previously occupied by a retailer for office per approved plans. Work to include relocation of exterior exit door, new interior bearing wall, construction of new accessible restrooms, Miscellaneous related interior finishes. (pc#511-04) rmh (DBSI OFFICE)(NORTHGATE SHOPPING CENTER)

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/21/20053/22/20053/22/2005APASS
DetailsTroy Cobbley
Fire alarm finaled. Hood suppression monitoring point added to panel 3/22/2005 12:59:16 PM
DOC - Permit Finaled3/22/20053/22/20053/22/2005PPASS
DetailsTroy Cobbley
Finaled by inspector at 3/22/2005 12:59:23 PM
INSP-Alarm Testing 2/1/20052/1/2005ADONE
Tested the FA panel signals to the monitoring station for the DBSI west riser room, acceptable. Dialer signals and smokes for the theatre, acceptable. Tested new phone lines at the Early Learning Center (improperly connected initially) but repaired and acceptable.

The items outstanding are:

DBSI west flow switch
Mongolian BBQ cooking hood monitoring point.
INSP-Alarm Testing 1/28/20051/28/2005PDONE
Tested previous items that requried rework all passed except the water flow on DBSI east sprinkler riser room.
INSP-Final Inspection1/27/20051/28/20051/28/2005PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 1/27/2005 at 4:42:33 PM. Contact: ###-####.

All duct detectors were smoked and functioned properly. (the duct on the roof has an enclosure, needs to have holes drilled to allow air to circulate around the pc board)

All forward flow test valves were wired to the backflow preventer input...they will be disconnected.

Zone labeling needs to be changed.

East side of facility.

West riser room smoke and pull had addresses reversed.

East riser room backflow and main flow were wired incorrectly.

East water flow requires adjustment (> 90 sec), Simplex has been called, apparently something is wrong with the flow switch.

West side of facility, tested all tampers and waterflows, exceptable.
Case Summary  1/28/2005 DONE
INSP-Final Inspection1/26/20051/27/20051/27/2005ACANC
DetailsRick Jackson
Scheduled by a contractor via Hello! on 1/26/2005 at 9:23:30 AM. Contact: ###-####. Rescheduled for 1/28 1/27/2005 9:03:12 AM
Issue and Print Permit  1/24/2005 DONE
Alarm Plan Check  1/14/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  1/14/2005 DONE
Permit Ready to Issue  1/14/2005 DONE
Inspection Record Card- Fire1/14/2005 1/14/2005 DONE
Telephone call  1/14/2005 DONE
Spoke with dave and told him that permit is ready & fees///1/14/05 9:25am BAS
INSP-Final Inspection1/10/20051/11/20051/11/2005AFAIL
DetailsTroy Cobbley
The zone labels for the tampers and riser rooms for learning center need changed to be more specific as to device and location. Tamper switches come in as troubles on this system too. The system in the theatres was not tested. Inspection for the new system was started at the duct detectors in DBSI's space. At the first detector inspected I found that the detector was not mounted in the air stream and upon closer inspection found that the detector was barely mounted to the duct and basicaly came off the ductwork into my hand. The sample tube was installed backwards and upside down and the foam donut seals were lying unistalled in a bag on the ceiling. Inspection was stopped. Resubmittals are also required due to additional anti-freeze tamper switches existing but not shown on the plans. 1/11/2005 2:08:57 PM
Plan resubmittals received  1/11/2005 DONE
Issue permit  10/22/2004 DONE
Plan assigned to (Mary)9/30/2004 10/21/2004 DONE
Alarm Plan Check  10/21/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  10/21/2004 DONE
Permit Ready to Issue  10/21/2004 DONE
Inspection Record Card- Fire10/21/2004 10/21/2004 DONE
Telephone call  10/21/2004 DONE
Left message for Dave that permit is ready & fees///10/21/04 8:35am BAS
Plan resubmittals received  10/14/2004 DONE
Alarm Plan Check  10/5/2004 FAIL
The submitted plans do not address the FA system installed in the E occupancy. Per IFC907.2.3, When automatic sprinkler systems or smoke detectors are installed, such systems or detectors hsall be connected to the building fire alarm system. Therefore, the sprinkler monitoring for Bldg #1 should activate the existing fire alarm system notification to evacuate the personnel. A meeting is being arranged to discuss options with bldg manager , Sam and myself.
Telephone call  10/5/2004 DONE
Phoned Dave (ADT) to inform him of the situation. I stated the submitted plans are not code compliant and we discussed some options. He is aware that I will contact Greg Beall (DBSI) to schedule a meeting to discuss the options.
INSP-Final Inspection10/4/200410/4/200410/4/2004PPART
DetailsTroy Cobbley
A temporary occupancy was given with dave millers and teresa's permission until the fire alarm and fire sprinklering of the outside canopies have been finished
Application received  9/30/2004