INSP-Final Inspection | 11/15/2004 | 11/15/2004 | 11/15/2004 | P | PASS |
Rick Jackson
|
|
|
Permit finaled 11/15/2004 1:21:34 PM
|
DOC - Permit Finaled | 11/15/2004 | 11/15/2004 | 11/15/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 11/15/2004 1:21:38 PM
|
INSP-Final Inspection | 11/9/2004 | 11/12/2004 | 11/12/2004 | A | PART |
Rick Jackson
|
|
|
Hank; Phone #: ###-#### Internet Inspection Request from: Jan Rice This is a new Piranha Ansul system that includes the new water flow valve that is to remain locked for proper operation after the agent flows; the electrical/gas valve shut down on activation; install K-class extinguisher; the appliance were installed backwards from what was shown on plans - approved as nozzles are spaced per Ansul to provide complete coverage; will need air balance report 11/12/2004 10:30:47 AM
|
Permit Ready to Issue | | | 10/1/2004 | | DONE |
|
|
|
|
Issue and Print Permit | | | 10/1/2004 | | DONE |
|
|
|
|
Application received | | | 9/30/2004 | | |
|
|
|
|