INSP-Final Inspection | 10/25/2004 | 10/26/2004 | 10/26/2004 | A | FAIL |
Troy Cobbley
|
|
|
Strobe installed is a 15/75 which is overspaced. Plans show 30cd. 10/26/2004 9:23:02 AM
|
INSP-Final Inspection | 10/26/2004 | 10/26/2004 | 10/26/2004 | P | PASS |
Troy Cobbley
|
|
|
Fire alarm finaled 10/26/2004 12:57:26 PM
|
DOC - Permit Finaled | 10/26/2004 | 10/26/2004 | 10/26/2004 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 10/26/2004 12:57:29 PM
|
Issue and Print Permit | | | 10/22/2004 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 10/6/2004 | | 10/20/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/20/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/20/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/20/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/20/2004 | | 10/20/2004 | | DONE |
|
|
|
|
Telephone call | | | 10/20/2004 | | |
|
|
|
Spoke with Charlie and told him that permit is ready & fees///10/20/04 2:00pm BAS
|
Plan resubmittals received | | | 10/19/2004 | | DONE |
|
|
|
Received fax from Charlie, Simplex; emergency generator information and fuel agreement.
|
Telephone call | | | 10/18/2004 | | DONE |
|
|
|
Left a message for Charlie requesting generator information and fuel agreement.
|
Plan resubmittals received | | | 10/14/2004 | | DONE |
|
|
|
Received fax from Charlie, Simplex; notes for the drawing.
|
Telephone call | | | 10/13/2004 | | DONE |
|
|
|
Phone message to Charlie Bayne (Simplex-Grinnell) the FA plans have keyed notes related to them, but there are no notes on the plans.
|
Application received | | | 10/6/2004 | | |
|
|
|
|