Permit Information
Permit NumberFIR04-00626
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 1379 N CLOVERDALE RD
Project NameSPR TUMBLE TIME GYMNASTICS
Customer Number 
ePlanReview 
Description
Tumble Time Gymnastics * To install a complete overhead fire sprinkler system in a new 12,554-ft/2 two story pre-engineered Type VB fully fire sprinklered gymnastics facility. Fire sprinklers are used for area and story increase. Area of the first floor is 10,167-ft/2 area of the second floor is 2,387-ft/2. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-00888.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/21/20051/21/20051/21/2005PPASS
DetailsTroy Cobbley
fire sprinklers finaled
DOC - Permit Finaled1/21/20051/21/20051/21/2005PPASS
DetailsTroy Cobbley
Finaled by inspector at 1/21/2005 4:11:44 PM
INSP-Sprinkler Rough-in/Hydro1/17/20051/18/20051/18/2005PPASS
DetailsTroy Cobbley
Overhead hydro test passed 1/18/2005 3:38:36 PM
INSP-Final Inspection1/17/20051/18/20051/18/2005PFAIL
DetailsTroy Cobbley
Need interconnections with the fire alarm system tested and the 200 degree upright in the riser room replaced with at 155 1/18/2005 3:57:38 PM
Issue and Print Permit  1/7/2005 DONE
Permit Ready to Issue  1/5/2005 DONE
Inspection Record Card- Fire1/5/2005 1/5/2005 DONE
Telephone call  1/5/2005 DONE
Left message for Randy that permit is ready & fees///1/5/05 8;10am BAS
Sprinkler Plan Check12/30/2004 1/4/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  1/4/2005 DONE
Plan resubmittals received  12/30/2004 DONE
INSP-Sprinkler Rough-in/Hydro12/17/200412/20/200412/20/2004PPART
DetailsTroy Cobbley
Upright sprinkler head is overspaced under the east stairway. Provide the correct size of hanger rings on the trapeze and resubmit plans showing the steel pipe instead of the plastic and the branchline that was added 12/20/2004 12:04:59 PM
INSP-Supply line flush12/15/200412/15/200412/15/2004PPASS
DetailsTroy Cobbley
Underground supply line hydro test passed 12/15/2004 3:01:11 PM
INSP-Sprinkler Rough-in/Hydro12/15/200412/15/200412/15/2004PPART
DetailsTroy Cobbley
Restrooms and riser room is ok to cover 12/15/2004 3:01:40 PM
Issue and Print Permit  10/27/2004  
Telephone call  10/26/2004 DONE
left mess that permit is ready
Permit Ready to Issue  10/26/2004  
Inspection Record Card- Fire10/26/2004 10/26/2004 DONE
Plan assigned to (Bill)10/11/2004 10/22/2004 DONE
Sprinkler Plan Check10/11/2004 10/22/2004 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  10/22/2004 DONE
Application received  10/11/2004  
Plan assigned to (Bill)12/30/2004    
DetailsBill Alexander