Permit Information
Permit NumberFIR04-00645
StatusFinaled
Name NORTHWEST SALES COMPANY
Site Address 999 W MAIN ST
Project Namealm - ONE CAPITAL CNTR-3RD FLR
Customer Number 
ePlanReview 
Description
To provide total coverage notification throughout the entire 3rd floor. As part of the fire alarm upgrade (10/25/2004), this floor is to be brought up to 2000IFC and 2002NFPA 72 requirements. The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, elevator recall/shutdown, high rise requirements and total coverage notification throughout.

The associated building permit (BLD 04-01253) is to remodel the 3rd floor (17,073 square feet) of an existing high-rise building for a whole floor tenant (15,900 net square feet). For exit separation reasons, a 2-hr fire barrier intended to function as a horizontal exit will be constructed to divide the floor into two egress areas. Work is to include interior nonbearing walls, 2-hr fire barrier walls with fire doors, interior doors and windows, and glass block walls all per the approved drawings and the plan review report on file. The restrooms are also being upgraded to be accessible to the disabled. The location of fire sprinkler heads shall comply with NFPA 13-2002 as regulated by the Fire Department. **CJW** (J R SIMPLOT COMPANY - 3RD FLOOR) This building is fire sprinklered because it is a high-rise.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Alarm Testing11/23/200411/24/200411/24/2004PPASS
DetailsRick Jackson
Rick let me know what time works for you so that I can schedule it with the building management Internet Inspection Request from: Rick Groom Verified detectors added at horizontal exit doors; third floor changes to be submitted with core upgrade plans 11/24/2004 11:28:03 AM
DOC - Permit Finaled11/24/200411/24/200411/24/2004APASS
DetailsRick Jackson
Finaled by inspector at 11/24/2004 11:28:11 AM
INSP-Final Inspection11/16/200411/16/200411/16/2004APART
DetailsRick Jackson
Smoke detectors required at doors with hold opens; Per Mary resubmittals not required under this permit but to be included in the core upgrade agreement 11/16/2004 12:04:46 PM
CHANGE STATUS TO (ISS)  11/15/2004  
Rick acidentally doc finaled///11/15/04 BAS
INSP-Alarm Testing11/10/200411/12/200411/12/2004APASS
DetailsRick Jackson
Rick let me know what time works for you so that I can get it scheduled on my side. thanks Internet Inspection Request from: Rick Groom
INSP-Alarm Testing11/8/200411/9/200411/9/2004PFAIL
DetailsRick Jackson
Rick we would like to schedule this for 4pm if possible. thanks; Phone #: ###-#### Internet Inspection Request from: Rick Groom Doors not releasing on alarm 11/9/2004 5:25:20 PM
Plan assigned to (Mary)10/15/2004 11/2/2004 DONE
Alarm Plan Check  11/2/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  11/2/2004 DONE
Permit Ready to Issue  11/2/2004 DONE
Inspection Record Card- Fire11/2/2004 11/2/2004 DONE
Telephone call  11/2/2004 DONE
Spoke with David and told him that permit is ready & fees///11/02/04 3:20pm BAS
Issue and Print Permit  11/2/2004 DONE
Plan resubmittals received  10/29/2004  
Application received  10/15/2004