Permit NumberFIR04-00650
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 7221 W POPLAR ST
Project Namealm - Idaho Youth Ranch
Customer NumberHAYS HOUSE II
ePlanReview 
Description
To provide a required manual fire alarm system. The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, door release (security access/egress doors), cooking hood monitoring, automatic detection and notification throughout.

The associated building permit (BLD 04-03049) is to construct a new 7450 square foot, one story wood framed group home 20 residents plus staff. This permit also includes the construction of a 615 square foot, one story wood framed garage and related site improvements. All construction per the approved plans and attached comment list. All construction per the approved plans and attached comment list. There is an approved alternate on file for allowing the corridors to be nonfire-resistive rated. Part of the alternate requires the installation of a full NFPA 13 sprinkler system with quick response heads throughout the building. CUP03-00012/PC#789-03/JCM Idaho Youth Ranch, Hays House II *
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
(F) Reprint permit  10/3/2005 DONE
DOC - Permit Finaled  10/3/2005 DONE
Alarm Plan Check  9/30/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  9/30/2005 DONE
Permit Ready to Issue  9/30/2005 DONE
Telephone call  9/30/2005 DONE
Spoke with John and told him that permit is ready & fees///9/30/05 10:05 AM BAS
INSP-Final Inspection9/21/20059/22/20059/22/2005APASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing9/16/20059/21/20059/21/2005PFAIL
DetailsTroy Cobbley
Signage at the egress controlled doors per IFC 1008.1.8.6
Plan resubmittals received  9/19/2005 DONE
INSP-Alarm Testing9/15/20059/16/20059/16/2005AFAIL
DetailsTroy Cobbley
Need knox key box, lower and test pull station at staff desk, provide second phone line, multiple a/vs are mounted too low, need to test all devices except facp, nac and hood.
FIR-Aging Inspection2/21/20052/21/20052/21/2005 NR
DetailsTroy Cobbley
work in progress 2/22/2005 3:17:42 PM
Permit Ready to Issue  11/22/2004 DONE
Inspection Record Card- Fire11/22/2004 11/22/2004 DONE
Telephone call  11/22/2004 DONE
Left message with Kevin that permit is ready & no fees///11/22/04 8:10am BAS
Issue and Print Permit  11/22/2004 DONE
Plan assigned to (Mary)10/18/2004 11/19/2004 DONE
Alarm Plan Check  11/19/2004 PASS
Approved pending field inspection of fire alarm permit comments.
Plan resubmittals received  11/19/2004 DONE
Received battery cut sheets and voltage drop calc for FACP NAC #1 via fax.
PLANS/APPL TAKEN TO FRONT DESK  11/19/2004 DONE
Telephone call  11/18/2004 DONE
Left a message to have John Lopez call. There is no VD calc for NAC#1 on the FACP. Request for him to fax it to me.
Plan resubmittals received  11/12/2004 DONE
Plan resubmittals received  11/1/2004 DONE
Received owners name from John Lopez, Fire Sentry: Gerry Hine, ###-#### fax: ###-####.
Alarm Plan Check  11/1/2004 FAIL
Resubmittal required. Faxed comments to John Lopez (Fire Sentry) and Shawn Meadorer (Synergy).
Telephone call  10/26/2004 DONE
To John Lopez, Fire Sentry, just a reminder that I will require the owners name, phone and fax for the IDaho Youth Ranch Hays House #2.
Application received  10/18/2004