(F) Reprint permit | | | 10/3/2005 | | DONE |
|
|
|
|
DOC - Permit Finaled | | | 10/3/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/30/2005 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/30/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/30/2005 | | DONE |
|
|
|
|
Telephone call | | | 9/30/2005 | | DONE |
|
|
|
Spoke with John and told him that permit is ready & fees///9/30/05 10:05 AM BAS
|
INSP-Final Inspection | 9/21/2005 | 9/22/2005 | 9/22/2005 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Alarm Testing | 9/16/2005 | 9/21/2005 | 9/21/2005 | P | FAIL |
Troy Cobbley
|
|
|
Signage at the egress controlled doors per IFC 1008.1.8.6
|
Plan resubmittals received | | | 9/19/2005 | | DONE |
|
|
|
|
INSP-Alarm Testing | 9/15/2005 | 9/16/2005 | 9/16/2005 | A | FAIL |
Troy Cobbley
|
|
|
Need knox key box, lower and test pull station at staff desk, provide second phone line, multiple a/vs are mounted too low, need to test all devices except facp, nac and hood.
|
FIR-Aging Inspection | 2/21/2005 | 2/21/2005 | 2/21/2005 | | NR |
Troy Cobbley
|
|
|
work in progress 2/22/2005 3:17:42 PM
|
Permit Ready to Issue | | | 11/22/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/22/2004 | | 11/22/2004 | | DONE |
|
|
|
|
Telephone call | | | 11/22/2004 | | DONE |
|
|
|
Left message with Kevin that permit is ready & no fees///11/22/04 8:10am BAS
|
Issue and Print Permit | | | 11/22/2004 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 10/18/2004 | | 11/19/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 11/19/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
Plan resubmittals received | | | 11/19/2004 | | DONE |
|
|
|
Received battery cut sheets and voltage drop calc for FACP NAC #1 via fax.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/19/2004 | | DONE |
|
|
|
|
Telephone call | | | 11/18/2004 | | DONE |
|
|
|
Left a message to have John Lopez call. There is no VD calc for NAC#1 on the FACP. Request for him to fax it to me.
|
Plan resubmittals received | | | 11/12/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 11/1/2004 | | DONE |
|
|
|
Received owners name from John Lopez, Fire Sentry: Gerry Hine, ###-#### fax: ###-####.
|
Alarm Plan Check | | | 11/1/2004 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to John Lopez (Fire Sentry) and Shawn Meadorer (Synergy).
|
Telephone call | | | 10/26/2004 | | DONE |
|
|
|
To John Lopez, Fire Sentry, just a reminder that I will require the owners name, phone and fax for the IDaho Youth Ranch Hays House #2.
|
Application received | | | 10/18/2004 | | |
|
|
|
|